FireCADCalc

Damper Leakage, Heat Loss and Sealing Efficiency

Gas leakage through a closed damper from duct area, sealing efficiency and pressure difference (Ganapathy), its heat loss and cost, and flow-basis efficiency.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperStack and chimneyFan and blower

Inputs

Examples: Ganapathy: 5 ft duct, 99.5 %, 7 in WC, 540 °FSquare 2 m duct, 99 %, 150 mmWC

Results

The flow-basis efficiency falls as the gas flow drops while the leakage, set by the pressure difference, stays the same.

Leakage3,520.0kg/h
Heat lost with the leakage340.60kW
Cost per hour (currency)5.8109
Sealing efficiency on a flow basis97.413%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Ganapathy: 5 ft duct, 99.5 %, 7 in WC, 540 °F. The inputs, in the units selected above:

InputValue
Duct cross-section1.8241 m²
Sealing efficiency on an area basis99.500 %
Differential pressure across the closed damper177.80 mmWC
Gas temperature282.22 °C
Normal gas flow (for the flow-basis efficiency)104,326 kg/h
Gas specific heat1.0886 kJ/(kg·K)
Ambient temperature26.667 °C
Fuel cost per GJ (currency)2.8435 -

Applying the formula below gives:

ResultValue
Leakage925.63 kg/h
Heat lost with the leakage71.528 kW
Cost per hour (currency)0.73219
Sealing efficiency on a flow basis99.113 %

Open this example in the calculator and change any input.

Formula

\(W_L = 2484\,A\,(100 - E)\sqrt{\frac{\Delta p}{460 + t}} \ \ (\mathrm{lb/h;\ ft^2,\ in\,WC,\ °F})\)

\(Q_L = W_L c_p (t - t_a), \quad E_f = 1 - \frac{W_L}{W_g}\)

Variables

Symbol Meaning SI unit
\(A\) Duct cross-section m²
\(E\) Sealing efficiency on an area basis -
\(\Delta p\) Differential pressure across the closed damper Pa
\(t\) Gas temperature K
\(W_g\) Normal gas flow (for the flow-basis efficiency) kg/s
\(c_p\) Gas specific heat J/(kg·K)
\(t_a\) Ambient temperature K
\(c_f\) Fuel cost per GJ (currency) -
\(W_L\) Leakage kg/s
\(Q_L\) Heat lost with the leakage W
\(C_L\) Cost per hour (currency) -
\(E_f\) Sealing efficiency on a flow basis -

Method and standards

Ganapathy's orifice-flow expression for damper leakage (C_d = 0.61, gas density 40/(460 + t)).

Where it is used

  • Isolation of HRSG bypass stacks and boiler ducts.
  • Specifying damper seal air.

Common mistakes

  • Mixing area-basis and flow-basis efficiencies.
  • Ignoring seal air fans.

Assumptions and limits

  • Gas density 40/(460 + t) lb/ft³ (flue gas of molar mass about 29 near 1 atm); other gases or pressures are not adjustable.
  • The cost is the heat lost times the price per GJ entered: enter the cost per GJ of heat (fuel price divided by boiler efficiency) for the fuel cost.
  • The flow-basis efficiency is not shown when the gas flow is zero.

References

  • Ganapathy
  • Steam Plant Calculations Manual
  • 2nd ed. (Marcel Dekker, 1993)
  • Q1.20 (gas leakage across dampers; orifice flow with C_d = 0.61)

Questions and answers

What is sealing efficiency?

The share of the duct area that is sealed when the damper is closed; makers quote 95–99.9 %.

Why two definitions?

On a flow basis the efficiency depends on the normal gas flow; on an area basis it does not.

What does Ganapathy's example give?

A 5 ft duct at 99.5 %, 7 in WC and 540 °F leaks about 2,040 lb/h.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.