Worked example
Example: Ganapathy: 5 ft duct, 99.5 %, 7 in WC, 540 °F. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Duct cross-section | 1.8241 m² |
| Sealing efficiency on an area basis | 99.500 % |
| Differential pressure across the closed damper | 177.80 mmWC |
| Gas temperature | 282.22 °C |
| Normal gas flow (for the flow-basis efficiency) | 104,326 kg/h |
| Gas specific heat | 1.0886 kJ/(kg·K) |
| Ambient temperature | 26.667 °C |
| Fuel cost per GJ (currency) | 2.8435 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Leakage | 925.63 kg/h |
| Heat lost with the leakage | 71.528 kW |
| Cost per hour (currency) | 0.73219 |
| Sealing efficiency on a flow basis | 99.113 % |
Open this example in the calculator and change any input.
Formula
\(W_L = 2484\,A\,(100 - E)\sqrt{\frac{\Delta p}{460 + t}} \ \ (\mathrm{lb/h;\ ft^2,\ in\,WC,\ °F})\)
\(Q_L = W_L c_p (t - t_a), \quad E_f = 1 - \frac{W_L}{W_g}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A\) | Duct cross-section | m² |
| \(E\) | Sealing efficiency on an area basis | - |
| \(\Delta p\) | Differential pressure across the closed damper | Pa |
| \(t\) | Gas temperature | K |
| \(W_g\) | Normal gas flow (for the flow-basis efficiency) | kg/s |
| \(c_p\) | Gas specific heat | J/(kg·K) |
| \(t_a\) | Ambient temperature | K |
| \(c_f\) | Fuel cost per GJ (currency) | - |
| \(W_L\) | Leakage | kg/s |
| \(Q_L\) | Heat lost with the leakage | W |
| \(C_L\) | Cost per hour (currency) | - |
| \(E_f\) | Sealing efficiency on a flow basis | - |
Method and standards
Ganapathy's orifice-flow expression for damper leakage (C_d = 0.61, gas density 40/(460 + t)).
Where it is used
- Isolation of HRSG bypass stacks and boiler ducts.
- Specifying damper seal air.
Common mistakes
- Mixing area-basis and flow-basis efficiencies.
- Ignoring seal air fans.
Assumptions and limits
- Gas density 40/(460 + t) lb/ft³ (flue gas of molar mass about 29 near 1 atm); other gases or pressures are not adjustable.
- The cost is the heat lost times the price per GJ entered: enter the cost per GJ of heat (fuel price divided by boiler efficiency) for the fuel cost.
- The flow-basis efficiency is not shown when the gas flow is zero.
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1993)
- Q1.20 (gas leakage across dampers; orifice flow with C_d = 0.61)
Questions and answers
What is sealing efficiency?
The share of the duct area that is sealed when the damper is closed; makers quote 95–99.9 %.
Why two definitions?
On a flow basis the efficiency depends on the normal gas flow; on an area basis it does not.
What does Ganapathy's example give?
A 5 ft duct at 99.5 %, 7 in WC and 540 °F leaks about 2,040 lb/h.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.