Worked example
Example: 1.1 % methane, LEL 4.4 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Lower explosive limit of the gas (by volume) | 4.4000 % |
| Gas concentration by volume | 1.1000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Concentration as a share of the LEL | 25.000 % |
| Concentration in ppm | 11,000 |
| Concentration at 20 % LEL | 0.88000 % |
Open this example in the calculator and change any input.
Formula
\(\%LEL = \frac{x}{LEL}, \quad c\,[\text{ppm}] = 10^6 x\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(LEL\) | Lower explosive limit of the gas (by volume) | - |
| \(x\) | Gas concentration by volume | - |
| \(\%LEL\) | Concentration as a share of the LEL | - |
| \(c\) | Concentration in ppm | - |
| \(x_{20}\) | Concentration at 20 % LEL | - |
Method and standards
Definitions.
Where it is used
- Gas detector alarms and calibration.
- Hot-work permits.
Common mistakes
- Mixing % LEL and % volume.
- Using a methane-calibrated detector for other gases.
Assumptions and limits
- Single gas in air. Readings at or above 20 % LEL and at or above 100 % LEL are flagged.
References
- Definition: % LEL = concentration / LEL
Questions and answers
What is 1.1 % methane in % LEL?
25 % LEL with an LEL of 4.4 % (22 % with 5 %).
What concentration is 20 % LEL?
0.88 % by volume of methane, 8800 ppm.
Which LEL should I use?
The one your detector is calibrated to; the tables differ.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.