Capacitor Bank Parallel Resonance Order

Harmonic order and frequency at which a capacitor bank resonates with the supply inductance, from short-circuit level, kvar and transformer data.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 400 kvar on 25 MVA bus1 Mvar on 25 MVA (5th)

Results

Resonance near the 5th harmonic: consider a detuned bank or a different size.

The ±0.5-order band is a screening rule of thumb. With a stepped (automatic) bank the order changes as √(S_sc/Q_C) with each step: check every step against the harmonics present, not only the full bank.

Resonant harmonic order5.0000
Resonant frequency250.00Hz
Order using transformer impedance only5.7735

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 400 kvar on 25 MVA bus. The inputs, in the units selected above:

InputValue
Short-circuit level at the bus25.000 MVA
Capacitor bank400.00 kvar
System frequency50.000 Hz
Transformer rating (for the check)1,600.0 kVA
Transformer impedance6.0000 %

Applying the formula below gives:

ResultValue
Resonant harmonic order7.9057
Resonant frequency395.28 Hz
Order using transformer impedance only8.1650

Open this example in the calculator and change any input.

Formula

\(h_r = \sqrt{\frac{S_{sc}}{Q_C}}, \quad f_r = h_rf, \quad h_{r,T} = \sqrt{\frac{S_T}{z_TQ_C}}\)

Variables

Symbol Meaning SI unit
\(S_{sc}\) Short-circuit level at the bus VA
\(Q_C\) Capacitor bank var
\(f\) System frequency 1/s
\(S_T\) Transformer rating (for the check) VA
\(z_T\) Transformer impedance -
\(h_r\) Resonant harmonic order -
\(f_r\) Resonant frequency 1/s
\(h_{r,T}\) Order using transformer impedance only -

Method and standards

Parallel resonance.

Where it is used

  • Capacitor bank sizing checks.
  • Explaining capacitor failures.

Common mistakes

  • Ignoring stages of an automatic bank (each step moves resonance).
  • Using upstream fault level that ignores the transformer.

Assumptions and limits

  • Inductive supply; resistance neglected.
  • Resonance within ±0.5 of the 3rd, 5th, 7th, 11th or 13th harmonic is flagged (a screening rule of thumb); for a stepped bank check each step.

References

  • Parallel resonance h_r = √(S_sc/Q_C) (IEEE 519 application practice)

Questions and answers

Why does a capacitor resonate with the supply?

The supply looks inductive from the bus; at h = √(S_sc/Q_C) the capacitor's reactance equals it and impedance peaks.

Why is the 5th the danger?

Six-pulse drives produce strong 5th and 7th harmonics; a resonance near them amplifies voltage distortion and overloads capacitors.

What do the defaults represent?

400 kvar on a bus with a 25 MVA short-circuit level, fed by a 1.6 MVA, 6 % transformer.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.