FireCADCalc

Detuned Capacitor Bank: Reactor Size and Tuning Frequency

Series reactor for a detuned capacitor bank from the detuning factor p, the resulting tuning frequency and order, the effective kvar and the capacitor voltage rise.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 100 kvar 480 V, 7 % on 415 V50 kvar 525 V, 14 %

Results

p = 7 % tunes to about 189 Hz (order 3.78) at 50 Hz, below the 5th harmonic; 14 % (order 2.67) where 3rd harmonics are significant. Capacitors must be rated for the raised voltage V_s/(1 − p).

Capacitor reactance per phase (star)2.3040Ω
Reactor reactance0.16128Ω
Reactor inductance0.51337mH
Tuning frequency188.98Hz
Tuning order3.7796
Effective output at system voltage80.377kvar
Voltage across the capacitor446.24V

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100 kvar 480 V, 7 % on 415 V. The inputs, in the units selected above:

InputValue
Capacitor rating at its rated voltage100.00 kvar
Capacitor rated voltage480.00 V
System voltage415.00 V
Detuning factor X_L/X_C7.0000 %
System frequency50.000 Hz

Applying the formula below gives:

ResultValue
Capacitor reactance per phase (star)2.3040 Ω
Reactor reactance0.16128 Ω
Reactor inductance0.51337 mH
Tuning frequency188.98 Hz
Tuning order3.7796
Effective output at system voltage80.377 kvar
Voltage across the capacitor446.24 V

Open this example in the calculator and change any input.

Formula

\(X_L = pX_C, \quad n_r = \frac{1}{\sqrt p}, \quad Q_{eff} = \frac{V_s^2}{X_C - X_L}, \quad V_{cap} = \frac{V_s}{1 - p}, \quad L = \frac{X_L}{2\pi f}\)

Variables

Symbol Meaning SI unit
\(Q_C\) Capacitor rating at its rated voltage var
\(V_C\) Capacitor rated voltage V
\(V_s\) System voltage V
\(p\) Detuning factor X_L/X_C -
\(f\) System frequency 1/s
\(X_C\) Capacitor reactance per phase (star) Ω
\(X_L\) Reactor reactance Ω
\(L\) Reactor inductance H
\(f_r\) Tuning frequency 1/s
\(n_r\) Tuning order -
\(Q_{eff}\) Effective output at system voltage var
\(V_{cap}\) Voltage across the capacitor V

Method and standards

Series LC relations.

Where it is used

  • Automatic power factor correction panels.
  • Sites with VFDs and rectifiers.

Common mistakes

  • Using 480 V capacitors at full nameplate kvar on 415 V.
  • Choosing p without a harmonic survey.

Assumptions and limits

  • Three-phase star equivalent.
  • A capacitor voltage V_s/(1 − p) above the capacitor's rated voltage is flagged.

References

  • Series LC detuning: n_r = 1/√p
  • V_cap = V/(1 − p) (power factor correction practice)

Questions and answers

Why detune a capacitor bank?

Plain capacitors can resonate with the supply at a harmonic and amplify it; a series reactor shifts the bank's resonance below the lowest harmonic present.

Why does the capacitor see more voltage?

The reactor's voltage is in opposition, so the capacitor voltage rises by 1/(1 − p).

What do the defaults represent?

A 100 kvar, 480 V capacitor with a 7 % reactor on a 415 V, 50 Hz system.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.