Shell-and-Tube Exchanger: Shells in Series for a Temperature Cross

Number of 1-2 shells in series needed to keep the LMTD correction factor above a minimum when outlet temperatures cross (Bowman's F).

Thermal power plantSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 200→90 against 30→130 (cross)150→90 against 30→100300→120 against 50→250, deep cross

Results

One 1-2 shell cannot achieve these temperatures, so F₁ is not shown.

Overall thermal effectiveness (cold side)0.58824
Capacity ratio1.1000
Shells in series needed2.0000
F with N shells0.87948
Corrected mean temperature difference57.053K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 200→90 against 30→130 (cross). The inputs, in the units selected above:

InputValue
Hot fluid in200.00 °C
Hot fluid out90.000 °C
Cold fluid in30.000 °C
Cold fluid out130.00 °C
Minimum acceptable F0.80000 -

Applying the formula below gives:

ResultValue
Overall thermal effectiveness (cold side)0.58824
Capacity ratio1.1000
Shells in series needed2.0000
F with N shells0.87948
Corrected mean temperature difference57.053 K

Open this example in the calculator and change any input.

Formula

\(P = \frac{t_{c,o} - t_{c,i}}{T_{h,i} - t_{c,i}}, \ R = \frac{T_{h,i} - T_{h,o}}{t_{c,o} - t_{c,i}}, \quad P_1 = \frac{1 - X}{R - X}, \ X = \left(\frac{1 - PR}{1 - P}\right)^{1/N}\)

\(F = \frac{\sqrt{R^2 + 1}}{R - 1}\frac{\ln\frac{1 - P_1}{1 - P_1R}}{\ln\frac{2 - P_1(R + 1 - \sqrt{R^2 + 1})}{2 - P_1(R + 1 + \sqrt{R^2 + 1})}}\)

Variables

Symbol Meaning SI unit
\(T_{h,in}\) Hot fluid in K
\(T_{h,out}\) Hot fluid out K
\(T_{c,in}\) Cold fluid in K
\(T_{c,out}\) Cold fluid out K
\(F_{min}\) Minimum acceptable F -
\(P\) Overall thermal effectiveness (cold side) -
\(R\) Capacity ratio -
\(F_1\) F with one shell -
\(N\) Shells in series needed -
\(F_N\) F with N shells -
\(F_N\Delta T_{lm}\) Corrected mean temperature difference K

Method and standards

Bowman's F for 1-2 shells, applied per shell for N shells in series.

Where it is used

  • Shell-and-tube exchanger layout.
  • Feed–effluent exchangers with close approaches.

Common mistakes

  • Accepting F below 0.75.
  • Ignoring the cross when only checking LMTD.

Assumptions and limits

  • Each shell one shell pass and an even number of tube passes.
  • When one shell cannot reach the temperatures at all, F₁ is not shown and a note says so.

References

  • Bowman
  • Mueller and Nagle
  • Trans. ASME 62: 283 (1940): F for 1-2 shells and N shells in series (Perry's Chemical Engineers' Handbook, 9th ed. (McGraw-Hill, 2019), sec. 11, Fig. 11-4)

Questions and answers

What is a temperature cross?

The cold outlet is hotter than the hot outlet; a single 1-2 shell cannot achieve it efficiently because part of its surface works in parallel flow.

Why add shells in series?

Each shell does part of the duty with less crossing, so the overall arrangement approaches true counterflow.

What do the defaults give?

200 → 90 °C against 30 → 130 °C: F is far too low in one shell; two shells in series give F about 0.88.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.