FireCADCalc

Thermic Fluid Heater Sizing from a List of Users

Thermic fluid heater rating and circulation flow from up to five users' loads, diversity, piping loss and margin, with the supply–return temperature drop.

Refinery and petrochemicalChemical and fertiliserThermic fluid heatingPulp and paperFood, dairy and textile

Inputs

Examples: 1.25 MW connectedFive users 2.5 MW

Results

Size the pump on the heater rating; users with their own control valves need the full flow only when all are open. 1 lakh kcal/h = 116.3 kW.

Connected load2,500.0kW
Demand with diversity and losses2,252.5kW
Heater rating2,477.8kW
Circulation flow123.89t/h
Heater rating (lakh kcal/h)21.305

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1.25 MW connected. The inputs, in the units selected above:

InputValue
User 1 load600.00 kW
User 2 load400.00 kW
User 3 load250.00 kW
User 4 load0 kW
User 5 load0 kW
Diversity factor90.000 %
Piping and tank heat loss share5.0000 %
Design margin15.000 %
Fluid specific heat at mean temperature2.5000 kJ/(kg·K)
Supply–return temperature difference25.000 K

Applying the formula below gives:

ResultValue
Connected load1,250.0 kW
Demand with diversity and losses1,181.2 kW
Heater rating1,358.4 kW
Circulation flow78.246 t/h
Heater rating (lakh kcal/h)11.680

Open this example in the calculator and change any input.

Formula

\(Q_d = k_d\sum Q_i\,(1 + f_l), \quad Q_h = Q_d(1 + m), \quad \dot m = \frac{Q_h}{c_p\Delta T}\)

Variables

Symbol Meaning SI unit
\(Q_1\) User 1 load W
\(Q_2\) User 2 load W
\(Q_3\) User 3 load W
\(Q_4\) User 4 load W
\(Q_5\) User 5 load W
\(k_d\) Diversity factor -
\(f_l\) Piping and tank heat loss share -
\(m\) Design margin -
\(c_p\) Fluid specific heat at mean temperature J/(kg·K)
\(\Delta T\) Supply–return temperature difference K
\(\Sigma Q\) Connected load W
\(Q_d\) Demand with diversity and losses W
\(Q_h\) Heater rating W
\(\dot m\) Circulation flow kg/s

Method and standards

Load summation.

Where it is used

  • New thermic fluid systems.
  • Adding users to an existing heater.

Common mistakes

  • Adding margin twice (users and heater).
  • Using a ΔT larger than the users can accept.

Assumptions and limits

  • Steady loads.
  • Piping and tank loss is taken as a share of the diversified load. A heat loss is closer to fixed for a given system and temperature, so with a low diversity factor the loss is understated; enter a larger share then.

References

  • Heat balance definitions (Q = ṁc_pΔT)

Questions and answers

Why a diversity factor?

Users rarely all draw peak load together; 0.8–0.9 is common for process plants.

Why rate heaters in lakh kcal/h?

It is the usual Indian rating; 1 lakh kcal/h is 116.3 kW.

What do the defaults give?

1.25 MW connected, 0.9 diversity, 5 % loss and 15 % margin: about 1.36 MW (11.7 lakh kcal/h) and 78 t/h of flow at 25 K.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.