Turbine Cycle with up to Four Feedwater Heaters: Heat Balance

Extraction flows for up to four closed feedwater heaters from shell pressures, TTD and DCA, then turbine power, final feedwater temperature and cycle heat rate.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserPulp and paper

Inputs

Examples: 200 t/h at 130 bar(a) 535 C, four heaters, 0.1 bar(a)60 t/h at 66 bar(a) 485 C, two heaters400 t/h at 160 bar(a) 540 C, three heaters, desuperheating top heater TTD -1

Accepted: 0.036 to 10,800 t/h
Accepted: 1 to 300 bar
Accepted: 100 to 800 °C
Accepted: 1 to 400 bar
Accepted: 0.01 to 2 bar
Accepted: 5 to 100 %
Accepted: 0.01 to 300 bar
Accepted: -5 to 30 K
Accepted: 0 to 30 K
Accepted: 0.01 to 300 bar
Accepted: -5 to 30 K
Accepted: 0 to 30 K
Accepted: 0.01 to 300 bar
Accepted: -5 to 30 K
Accepted: 0 to 30 K
Accepted: 0.01 to 300 bar
Accepted: -5 to 30 K
Accepted: 0 to 30 K
Accepted: 5 to 100 %

Results

All heaters are closed with drains cascaded to the next lower heater and the last drain to the condenser; feedwater flow equals throttle flow (no make-up, no reheat). Pump work and pressure losses in extraction lines are neglected. The no-heater case expands along one line of the same efficiency, which is slightly different from the sectioned line.

Heater 1: extraction steam flow40.833t/h
Heater 1: extraction enthalpy3,140.8kJ/kg
Heater 1: feedwater outlet temperature270.97°C
Heater 1: drain outlet temperature229.56°C
Heater 2: extraction steam flow71.526t/h
Heater 2: extraction enthalpy2,971.1kJ/kg
Heater 2: feedwater outlet temperature223.96°C
Heater 2: drain outlet temperature114.15°C
Heater 4: extraction steam flow34.188t/h
Heater 4: extraction enthalpy2,524.0kJ/kg
Heater 4: feedwater outlet temperature108.55°C
Heater 4: drain outlet temperature47.110°C
Steam to the condenser253.45t/h
Exhaust dryness0.83593
Final feedwater temperature270.97°C
Generator output105,270kW
Heat added in the boiler247,267kW
Turbine cycle heat rate8,456.0kJ/kWh
Cycle efficiency42.573%
Generator output with no heaters129,808kW
Heat rate with no heaters9,924.6kJ/kWh
Heat-rate improvement from the heaters14.797%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 200 t/h at 130 bar(a) 535 C, four heaters, 0.1 bar(a). The inputs, in the units selected above:

InputValue
Throttle steam flow (= feedwater flow)200.00 t/h
Throttle pressure (absolute)130.00 bar
Throttle temperature535.00 °C
Feedwater pressure through the heaters (absolute)160.00 bar
Condenser pressure (absolute)0.10000 bar
Expansion-line (section) isentropic efficiency82.000 %
Heater 1Closed heater, drains cascaded down
Heater 1: extraction (shell) pressure, absolute40.000 bar
Heater 1: terminal temperature difference2.0000 K
Heater 1: drain cooler approach6.0000 K
Heater 2Closed heater, drains cascaded down
Heater 2: extraction (shell) pressure, absolute18.000 bar
Heater 2: terminal temperature difference2.0000 K
Heater 2: drain cooler approach6.0000 K
Heater 3Closed heater, drains cascaded down
Heater 3: extraction (shell) pressure, absolute2.5000 bar
Heater 3: terminal temperature difference2.5000 K
Heater 3: drain cooler approach5.5000 K
Heater 4Closed heater, drains cascaded down
Heater 4: extraction (shell) pressure, absolute0.70000 bar
Heater 4: terminal temperature difference3.0000 K
Heater 4: drain cooler approach5.5000 K
Gearbox and generator efficiency97.000 %

Applying the formula below gives:

ResultValue
Heater 1: extraction steam flow17.614 t/h
Heater 1: extraction enthalpy3,142.0 kJ/kg
Heater 1: feedwater outlet temperature248.36 °C
Heater 1: drain outlet temperature211.12 °C
Heater 2: extraction steam flow25.947 t/h
Heater 2: extraction enthalpy2,975.9 kJ/kg
Heater 2: feedwater outlet temperature205.12 °C
Heater 2: drain outlet temperature130.91 °C
Heater 3: extraction steam flow10.877 t/h
Heater 3: extraction enthalpy2,656.8 kJ/kg
Heater 3: feedwater outlet temperature124.91 °C
Heater 3: drain outlet temperature92.432 °C
Heater 4: extraction steam flow10.900 t/h
Heater 4: extraction enthalpy2,487.6 kJ/kg
Heater 4: feedwater outlet temperature86.932 °C
Heater 4: drain outlet temperature51.308 °C
Steam to the condenser134.66 t/h
Exhaust dryness0.86775
Final feedwater temperature248.36 °C
Generator output51,851 kW
Heat added in the boiler130,745 kW
Turbine cycle heat rate9,077.6 kJ/kWh
Cycle efficiency39.658 %
Generator output with no heaters59,860 kW
Heat rate with no heaters10,779 kJ/kWh
Heat-rate improvement from the heaters15.783 %

Open this example in the calculator and change any input.

Formula

\(\dot m_j(h_j - h_{d,j}) + D_{j-1}(h_{d,j-1} - h_{d,j}) = \dot m_{fw}(h_{fw,j} - h_{fw,j+1}), \quad T_{fw,j} = T_{sat}(p_j) - TTD_j, \quad T_{d,j} = T_{fw,j+1} + DCA_j\)

\(P_{el} = \eta_g\sum_j\Big(\dot m_0 - \sum_{k<j}\dot m_k\Big)(h_{j-1} - h_j), \quad HR = \frac{\dot m_0(h_0 - h_{fw})}{P_{el}}\)

Variables

Symbol Meaning SI unit
\(\dot m_0\) Throttle steam flow (= feedwater flow) kg/s
\(p_0\) Throttle pressure (absolute) Pa
\(T_0\) Throttle temperature K
\(p_{fw}\) Feedwater pressure through the heaters (absolute) Pa
\(p_c\) Condenser pressure (absolute) Pa
\(\eta_t\) Expansion-line (section) isentropic efficiency -
\(\text{use}_1\) Heater 1 -
\(p_1\) Heater 1: extraction (shell) pressure, absolute Pa
\(TTD_1\) Heater 1: terminal temperature difference K
\(DCA_1\) Heater 1: drain cooler approach K
\(\text{use}_2\) Heater 2 -
\(p_2\) Heater 2: extraction (shell) pressure, absolute Pa
\(TTD_2\) Heater 2: terminal temperature difference K
\(DCA_2\) Heater 2: drain cooler approach K
\(\text{use}_3\) Heater 3 -
\(p_3\) Heater 3: extraction (shell) pressure, absolute Pa
\(TTD_3\) Heater 3: terminal temperature difference K
\(DCA_3\) Heater 3: drain cooler approach K
\(\text{use}_4\) Heater 4 -
\(p_4\) Heater 4: extraction (shell) pressure, absolute Pa
\(TTD_4\) Heater 4: terminal temperature difference K
\(DCA_4\) Heater 4: drain cooler approach K
\(\eta_g\) Gearbox and generator efficiency -
\(\dot m_1\) Heater 1: extraction steam flow kg/s
\(h_1\) Heater 1: extraction enthalpy J/kg
\(T_{fw,1}\) Heater 1: feedwater outlet temperature K
\(T_{d,1}\) Heater 1: drain outlet temperature K
\(\dot m_2\) Heater 2: extraction steam flow kg/s
\(h_2\) Heater 2: extraction enthalpy J/kg
\(T_{fw,2}\) Heater 2: feedwater outlet temperature K
\(T_{d,2}\) Heater 2: drain outlet temperature K
\(\dot m_3\) Heater 3: extraction steam flow kg/s
\(h_3\) Heater 3: extraction enthalpy J/kg
\(T_{fw,3}\) Heater 3: feedwater outlet temperature K
\(T_{d,3}\) Heater 3: drain outlet temperature K
\(\dot m_4\) Heater 4: extraction steam flow kg/s
\(h_4\) Heater 4: extraction enthalpy J/kg
\(T_{fw,4}\) Heater 4: feedwater outlet temperature K
\(T_{d,4}\) Heater 4: drain outlet temperature K
\(\dot m_c\) Steam to the condenser kg/s
\(x_c\) Exhaust dryness -
\(T_{fw}\) Final feedwater temperature K
\(P_{el}\) Generator output W
\(Q\) Heat added in the boiler W
\(HR\) Turbine cycle heat rate J/J
\(\eta_{cyc}\) Cycle efficiency -
\(P_{el,0}\) Generator output with no heaters W
\(HR_0\) Heat rate with no heaters J/J
\(\Delta HR\) Heat-rate improvement from the heaters -

Method and standards

Regenerative feed heating heat balance with IAPWS-IF97.

Where it is used

  • Checking extraction flows and heater performance in power and captive plants.
  • Effect of a heater out of service or a changed TTD on heat rate.
  • Preliminary cycle design.

Common mistakes

  • Listing heaters from low to high pressure.
  • Using gauge pressures.
  • Forgetting the drains cascading from higher heaters.

Assumptions and limits

  • Closed heaters only; no deaerator, reheat or make-up; pump work neglected.

Questions and answers

How are the extraction flows found?

From the top heater down: each heater's steam must supply the feedwater temperature rise less the heat brought in by the drains cascading from the heaters above it. The drain leaves each heater DCA above that heater's feedwater inlet temperature.

What sets each heater's outlet temperature?

The shell saturation temperature at the extraction pressure less the terminal temperature difference (TTD). Drain coolers make DCA positive; heaters with a desuperheating zone can have TTD near zero or slightly negative.

Why does feed heating improve heat rate if it costs power?

The extracted steam gives up its latent heat to the feedwater instead of to the condenser, so less fuel heat is needed per kWh even though the turbine makes less power for the same throttle flow.

What do the defaults represent?

200 t/h at 130 bar(a) and 535 °C, four closed heaters at 40, 18, 2.5 and 0.7 bar(a), 0.1 bar(a) condenser, 82 % expansion line: extractions of 17.6, 26.0, 10.9 and 10.9 t/h, final feedwater 248 °C, 51.9 MW and a cycle heat rate of 9,078 kJ/kWh, about 16 % better than with no heaters.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

IAPWS R7-97(2012) IF97 (steam and water properties), Heater energy balances with cascaded drains; turbine section-by-section energy balance

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.