FireCADCalc

Maximum Safe Fill for Thermal Expansion of a Liquid

Largest fill a tank or container can take at the filling temperature so the liquid stays below a set fill at the highest expected temperature.

Inputs

Examples: Illustrative 100 m3, beta 0.001, 15 to 50 CDiesel 50 m3, 20 to 45 CSolvent drum 0.2 m3, 10 to 55 C

Accepted: 0.001 to 100,000 m³
Accepted: 1E-5 to 0.005 1/K
Accepted: -53.15 to 126.85 °C
Accepted: -53.15 to 176.85 °C
Accepted: 50 to 100 %

Results

V(T) = V_f·exp(β(T − T_f)), constant β. Liquefied gases (LPG, ammonia) have large and strongly temperature-dependent β; use density tables there: φ_f = φ_max·ρ(T_max)/ρ(T_f). Container expansion is neglected (conservative).

Maximum fill at the filling temperature95.987%
Maximum volume to fill47.994m³
Expansion volume to the highest temperature1.0063m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 100 m3, beta 0.001, 15 to 50 C. The inputs, in the units selected above:

InputValue
Container volume100.00 m³
Liquid volumetric expansion coefficient0.001000 1/K
Filling temperature15.000 °C
Highest expected liquid temperature50.000 °C
Allowed fill at the highest temperature97.000 %

Applying the formula below gives:

ResultValue
Maximum fill at the filling temperature93.664 %
Maximum volume to fill93.664 m³
Expansion volume to the highest temperature3.3363 m³

Open this example in the calculator and change any input.

Formula

\(\phi_f = \phi_{max}e^{-\beta(T_{max} - T_f)}\)

Variables

Symbol Meaning SI unit
\(V\) Container volume m³
\(\beta\) Liquid volumetric expansion coefficient 1/K
\(T_f\) Filling temperature K
\(T_{max}\) Highest expected liquid temperature K
\(\phi_{max}\) Allowed fill at the highest temperature -
\(\phi_f\) Maximum fill at the filling temperature -
\(V_f\) Maximum volume to fill m³
\(\Delta V\) Expansion volume to the highest temperature m³

Method and standards

Fill limit.

Where it is used

  • Tank and tanker loading limits.
  • Drum and IBC filling.

Common mistakes

  • Using the filling temperature as the design maximum.
  • Using a constant β for liquefied gases.

Assumptions and limits

  • Constant expansion coefficient; rigid container.

References

  • Volumetric thermal expansion of liquids

Questions and answers

Why leave ullage?

A completely full closed container builds huge pressure when the liquid warms, because liquids are nearly incompressible.

Which liquids need most room?

Liquefied gases such as LPG expand about 0.2–0.3 % per kelvin, roughly three times as much as petrol.

What do the defaults represent?

An illustrative 100 m³ tank filled with a light hydrocarbon (β = 0.001 /K) at 15 °C, never to exceed 97 % full at 50 °C.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Perry's Chemical Engineers' Handbook (McGraw-Hill), sec. 2

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.