Bund (Dike) Capacity and Wall Height around Tanks

Required bund capacity from the largest tank and total stored volume, and the bund wall height for a bund area after deducting tanks standing inside it.

Inputs

Examples: Illustrative 40 x 30 m bundSingle tank bundMany small tanks

Accepted: 0.1 to 1,000,000 m³
Accepted: 0.1 to 10,000,000 m³
Accepted: 50 to 200 %
Accepted: 0 to 100 %
Accepted: 1 to 1,000 m
Accepted: 1 to 1,000 m
Accepted: 0 to 50
Accepted: 0 to 100 m
Accepted: 0 to 2,000 mm

Results

Capacity = max(f₁·largest tank, f₂·total); tanks other than the largest displace bund volume up to the liquid height. Take f₁, f₂, freeboard and wall height limits from the regulation that applies; allow for rainwater and firefighting water where required.

Required bund capacity550.00m³
Effective bund area400.00m²
Liquid height needed1.3750m
Bund wall height with freeboard1.5250m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 40 x 30 m bund. The inputs, in the units selected above:

InputValue
Largest tank volume1,000.0 m³
Total volume of all tanks in the bund2,500.0 m³
Factor on largest tank110.00 %
Factor on total volume25.000 %
Bund length (inside)40.000 m
Bund width (inside)30.000 m
Other tanks standing in the bund2.0000 -
Diameter of the other tanks10.000 m
Freeboard200.00 mm

Applying the formula below gives:

ResultValue
Required bund capacity1,100.0 m³
Effective bund area1,042.9 m²
Liquid height needed1.0547 m
Bund wall height with freeboard1.2547 m

Open this example in the calculator and change any input.

Formula

\(V_{req} = \max(f_1V_{max}, f_2V_{tot}), \quad h = \frac{V_{req}}{LW - n\pi D_o^2/4}\)

Variables

Symbol Meaning SI unit
\(V_{max}\) Largest tank volume m³
\(V_{tot}\) Total volume of all tanks in the bund m³
\(f_1\) Factor on largest tank -
\(f_2\) Factor on total volume -
\(L\) Bund length (inside) m
\(W\) Bund width (inside) m
\(n\) Other tanks standing in the bund -
\(D_o\) Diameter of the other tanks m
\(h_{fb}\) Freeboard m
\(V_{req}\) Required bund capacity m³
\(A_e\) Effective bund area m²
\(h\) Liquid height needed m
\(h_w\) Bund wall height with freeboard m

Method and standards

Bund sizing.

Where it is used

  • Tank farm layout.
  • Checking existing bunds after adding tanks.

Common mistakes

  • Forgetting displacement by other tanks.
  • Ignoring rainwater accumulation.

Assumptions and limits

  • Flat bund floor; vertical walls.

References

  • Secondary containment volume with tank displacement
  • Common secondary-containment practice

Questions and answers

Why deduct the other tanks?

Their bases occupy bund floor area, so spilled liquid rises faster; only the largest tank's own footprint is not deducted because it is the one assumed to leak.

Why 110 %?

A margin over the largest tank allows for rainwater, foam and surge; many rules also require a share of the total stored volume.

What do the defaults represent?

An illustrative 40 × 30 m bund holding a 1,000 m³ tank and two others of 10 m diameter, 2,500 m³ in total, with 0.2 m freeboard.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.