Worked example
Example: Illustrative 40 x 30 m bund. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Largest tank volume | 1,000.0 m³ |
| Total volume of all tanks in the bund | 2,500.0 m³ |
| Factor on largest tank | 110.00 % |
| Factor on total volume | 25.000 % |
| Bund length (inside) | 40.000 m |
| Bund width (inside) | 30.000 m |
| Other tanks standing in the bund | 2.0000 - |
| Diameter of the other tanks | 10.000 m |
| Freeboard | 200.00 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Required bund capacity | 1,100.0 m³ |
| Effective bund area | 1,042.9 m² |
| Liquid height needed | 1.0547 m |
| Bund wall height with freeboard | 1.2547 m |
Open this example in the calculator and change any input.
Formula
\(V_{req} = \max(f_1V_{max}, f_2V_{tot}), \quad h = \frac{V_{req}}{LW - n\pi D_o^2/4}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_{max}\) | Largest tank volume | m³ |
| \(V_{tot}\) | Total volume of all tanks in the bund | m³ |
| \(f_1\) | Factor on largest tank | - |
| \(f_2\) | Factor on total volume | - |
| \(L\) | Bund length (inside) | m |
| \(W\) | Bund width (inside) | m |
| \(n\) | Other tanks standing in the bund | - |
| \(D_o\) | Diameter of the other tanks | m |
| \(h_{fb}\) | Freeboard | m |
| \(V_{req}\) | Required bund capacity | m³ |
| \(A_e\) | Effective bund area | m² |
| \(h\) | Liquid height needed | m |
| \(h_w\) | Bund wall height with freeboard | m |
Method and standards
Bund sizing.
Where it is used
- Tank farm layout.
- Checking existing bunds after adding tanks.
Common mistakes
- Forgetting displacement by other tanks.
- Ignoring rainwater accumulation.
Assumptions and limits
- Flat bund floor; vertical walls.
References
- Secondary containment volume with tank displacement
- Common secondary-containment practice
Questions and answers
Why deduct the other tanks?
Their bases occupy bund floor area, so spilled liquid rises faster; only the largest tank's own footprint is not deducted because it is the one assumed to leak.
Why 110 %?
A margin over the largest tank allows for rainwater, foam and surge; many rules also require a share of the total stored volume.
What do the defaults represent?
An illustrative 40 × 30 m bund holding a 1,000 m³ tank and two others of 10 m diameter, 2,500 m³ in total, with 0.2 m freeboard.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.