Worked example
Example: FD fan 20 m³/s, inlet 1.8 m², outlet 1.2 m², -50 / +2 900 Pa. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Volume flow | 72,000 m³/h |
| Gas density | 1.1500 kg/m³ |
| Flow area at the inlet measuring plane | 1.8000 m² |
| Flow area at the outlet measuring plane | 1.2000 m² |
| Static pressure at the inlet (gauge, negative for suction) | -5.0986 mmWC |
| Static pressure at the outlet (gauge) | 295.72 mmWC |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fan total pressure | 309.86 mmWC |
| Fan static pressure | 293.58 mmWC |
| Air power on fan total pressure | 60.775 kW |
| Inlet velocity | 11.111 m/s |
| Outlet velocity | 16.667 m/s |
| Inlet velocity pressure | 7.2387 mmWC |
| Outlet velocity pressure | 16.287 mmWC |
| Inlet total pressure (gauge) | 2.1401 mmWC |
| Outlet total pressure (gauge) | 312.00 mmWC |
Open this example in the calculator and change any input.
Formula
\(v_1 = \frac{\dot V}{A_1} \qquad v_2 = \frac{\dot V}{A_2} \qquad p_{d1} = \frac{\rho v_1^2}{2} \qquad p_{d2} = \frac{\rho v_2^2}{2} \qquad p_{t1} = p_{s1} + p_{d1} \qquad p_{t2} = p_{s2} + p_{d2}\)
\(p_F = p_{t2} - p_{t1} \qquad p_{sF} = p_{s2} - p_{t1} \qquad P_a = \dot V\,p_F\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | volume flow | m³/s |
| \(\rho\) | gas density | kg/m³ |
| \(A_1\) | flow area at the inlet measuring plane | m² |
| \(A_2\) | flow area at the outlet measuring plane | m² |
| \(p_{s1}\) | static pressure at the inlet, gauge | Pa |
| \(p_{s2}\) | static pressure at the outlet, gauge | Pa |
| \(p_F\) | fan total pressure | Pa |
| \(p_{sF}\) | fan static pressure | Pa |
| \(P_a\) | air power on fan total pressure | W |
| \(v_1\) | inlet velocity | m/s |
| \(v_2\) | outlet velocity | m/s |
| \(p_{d1}\) | inlet velocity pressure | Pa |
| \(p_{d2}\) | outlet velocity pressure | Pa |
| \(p_{t1}\) | inlet total pressure, gauge | Pa |
| \(p_{t2}\) | outlet total pressure, gauge | Pa |
Method and standards
Fan pressure definitions of ISO 5801 (and AMCA 210) for incompressible flow, with mean velocities at the measuring planes.
Where it is used
- Converting fan data between static and total pressure.
- Fan selection from catalogue curves.
- Fan test analysis.
Common mistakes
- Mixing static and total efficiencies.
- Using the outlet area of the wrong duct.
- Ignoring velocity pressure at high outlet velocities.
Assumptions and limits
- Uniform velocity in each plane; with a distorted profile the true velocity pressure is higher.
- Incompressible; below about 2.5 kPa the error is negligible.
- Gauge pressures at both planes referred to the same atmosphere.
References
- ISO 5801 (fan performance, pressure definitions)
- AMCA 210
Questions and answers
What is the difference between fan static and total pressure?
Fan total pressure is the rise in total pressure from inlet to outlet. Fan static pressure is the outlet static pressure minus the inlet total pressure, so it leaves out the outlet velocity pressure. For an FD fan with 20 m³/s through a 1.2 m² outlet that difference is 160 Pa.
How do I get the fan pressure from site readings?
Enter the static pressures measured at the inlet and outlet (gauge; suction negative), the flow and the duct areas there. The calculator adds the velocity pressures.
Which pressure goes with which efficiency?
Fan total pressure with total efficiency; fan static pressure with static efficiency.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.