Fan and Duct System Curve Operating Point

Air flow and pressure where a fan curve p = p₀ − a Q² meets the duct system curve p = k Q², with the fan power, from a fan point and a system point.

Thermal power plantProcess steam and utilitiesSugar mill and cogeneration

Inputs

Examples: 1 500 Pa shut-off, 1 100 Pa at 10 m³/s; system 1 000 Pa at 10 m³/sDirty filter: system 1 400 Pa at 10 m³/sID fan: 6 kPa, 4.5 kPa at 40 m³/s; system 4 kPa at 40 m³/s

Results

A duct system with no static lift: resistance goes with Q². Real fan curves are not parabolas near stall; stay right of the peak.

Air flow at the operating point32,863m³/h
Pressure at the operating point11.667mbar
Shaft power15.215kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 500 Pa shut-off, 1 100 Pa at 10 m³/s; system 1 000 Pa at 10 m³/s. The inputs, in the units selected above:

InputValue
Fan shut-off pressure15.000 mbar
A fan flow on its curve36,000 m³/h
Fan pressure at that flow11.000 mbar
A system flow36,000 m³/h
System resistance at that flow10.000 mbar
Fan efficiency at the duty70.000 %

Applying the formula below gives:

ResultValue
Air flow at the operating point37,264 m³/h
Pressure at the operating point10.714 mbar
Shaft power15.843 kW

Open this example in the calculator and change any input.

Formula

\(p_{fan} = p_0 - aQ^2, \quad p_{sys} = kQ^2, \quad Q^* = \sqrt{\frac{p_0}{a + k}}\)

Variables

Symbol Meaning SI unit
\(p_0\) Fan shut-off pressure Pa
\(Q_f\) A fan flow on its curve m³/s
\(p_f\) Fan pressure at that flow Pa
\(Q_s\) A system flow m³/s
\(p_s\) System resistance at that flow Pa
\(\eta\) Fan efficiency at the duty -
\(Q\) Air flow at the operating point m³/s
\(p\) Pressure at the operating point Pa
\(P\) Shaft power W

Method and standards

Intersection of the two curves.

Where it is used

  • Fan selection and HVAC balancing.
  • Boiler draught fans.

Common mistakes

  • Static and total pressure mixed.
  • Extrapolating into stall.

Assumptions and limits

  • Parabolic curves.
  • Fan curve, system curve and efficiency on one pressure basis: fan total pressure with total efficiency, or fan static pressure with static efficiency.

References

  • Fan and system curves (Fan Engineering, Buffalo Forge; AMCA 200 terminology)

Questions and answers

Why does a dirty filter cut the flow?

It steepens the system curve, so it meets the fan curve at lower flow.

Why stay right of the peak?

Left of it the fan can surge and stall.

How do I get a fan point?

From the maker's curve at the fan's speed and density.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.