Worked example
Example: 1 500 Pa shut-off, 1 100 Pa at 10 m³/s; system 1 000 Pa at 10 m³/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fan shut-off pressure | 15.000 mbar |
| A fan flow on its curve | 36,000 m³/h |
| Fan pressure at that flow | 11.000 mbar |
| A system flow | 36,000 m³/h |
| System resistance at that flow | 10.000 mbar |
| Fan efficiency at the duty | 70.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air flow at the operating point | 37,264 m³/h |
| Pressure at the operating point | 10.714 mbar |
| Shaft power | 15.843 kW |
Open this example in the calculator and change any input.
Formula
\(p_{fan} = p_0 - aQ^2, \quad p_{sys} = kQ^2, \quad Q^* = \sqrt{\frac{p_0}{a + k}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_0\) | Fan shut-off pressure | Pa |
| \(Q_f\) | A fan flow on its curve | m³/s |
| \(p_f\) | Fan pressure at that flow | Pa |
| \(Q_s\) | A system flow | m³/s |
| \(p_s\) | System resistance at that flow | Pa |
| \(\eta\) | Fan efficiency at the duty | - |
| \(Q\) | Air flow at the operating point | m³/s |
| \(p\) | Pressure at the operating point | Pa |
| \(P\) | Shaft power | W |
Method and standards
Intersection of the two curves.
Where it is used
- Fan selection and HVAC balancing.
- Boiler draught fans.
Common mistakes
- Static and total pressure mixed.
- Extrapolating into stall.
Assumptions and limits
- Parabolic curves.
- Fan curve, system curve and efficiency on one pressure basis: fan total pressure with total efficiency, or fan static pressure with static efficiency.
References
- Fan and system curves (Fan Engineering, Buffalo Forge; AMCA 200 terminology)
Questions and answers
Why does a dirty filter cut the flow?
It steepens the system curve, so it meets the fan curve at lower flow.
Why stay right of the peak?
Left of it the fan can surge and stall.
How do I get a fan point?
From the maker's curve at the fan's speed and density.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.