Worked example
Example: ID fan 30 m³/s, 2.5 kPa, 120 kW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Volume flow at fan inlet conditions | 108,000 m³/h |
| Fan static pressure rise | 2,500.0 Pa |
| Fan outlet area | 1.2000 m² |
| Air or gas density at the fan | 1.1000 kg/m³ |
| Measured motor input | 120.00 kW |
| Motor and drive efficiency | 94.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Outlet velocity pressure | 343.75 Pa |
| Fan total pressure | 2,843.8 Pa |
| Air power (total) | 85.312 kW |
| Static efficiency | 66.489 % |
| Total efficiency | 75.632 % |
Open this example in the calculator and change any input.
Formula
\(p_v = \frac{\rho}{2}\left(\frac{Q}{A_o}\right)^2, \quad \Delta p_t = \Delta p_s + p_v, \quad \eta_t = \frac{Q\Delta p_t}{\eta_mP_{in}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Volume flow at fan inlet conditions | m³/s |
| \(\Delta p_s\) | Fan static pressure rise | Pa |
| \(A_o\) | Fan outlet area | m² |
| \(\rho\) | Air or gas density at the fan | kg/m³ |
| \(P_{in}\) | Measured motor input | W |
| \(\eta_m\) | Motor and drive efficiency | - |
| \(p_v\) | Outlet velocity pressure | Pa |
| \(\Delta p_t\) | Fan total pressure | Pa |
| \(P_a\) | Air power (total) | W |
| \(\eta_s\) | Static efficiency | - |
| \(\eta_t\) | Total efficiency | - |
Method and standards
Fan definitions.
Where it is used
- Fan performance checks.
- Energy audits of FD and ID fans.
Common mistakes
- Mixing inlet and outlet conditions.
- Ignoring the motor efficiency.
Assumptions and limits
- Incompressible; steady.
- An efficiency above 100 % is flagged as a measurement or input error.
References
- Fan pressure and efficiency definitions (fan total = static + outlet velocity pressure)
Questions and answers
Why is total efficiency higher than static?
Total efficiency credits the fan with the kinetic energy in its outlet air; static efficiency does not.
Which should I compare?
The same one the maker quotes; boiler fans are often quoted on total pressure.
What do the defaults represent?
An induced-draught fan moving 30 m³/s at 2.5 kPa static with 120 kW input.