Fan Static and Total Efficiency from a Site Test

Fan static and total efficiency from measured flow, static pressure rise, outlet velocity pressure and shaft or motor power, with the air power.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: ID fan 30 m³/s, 2.5 kPa, 120 kWFD fan 20 m³/s, 4 kPa, 110 kW

Results

Fan static pressure is fan total pressure minus outlet velocity pressure (ISO 5801 / AMCA definitions). Compare total efficiency with the maker's curve at the same flow.

Outlet velocity pressure230.00Pa
Fan total pressure4,230.0Pa
Air power (total)84.600kW
Static efficiency76.555%
Total efficiency80.957%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: ID fan 30 m³/s, 2.5 kPa, 120 kW. The inputs, in the units selected above:

InputValue
Volume flow at fan inlet conditions108,000 m³/h
Fan static pressure rise2,500.0 Pa
Fan outlet area1.2000 m²
Air or gas density at the fan1.1000 kg/m³
Measured motor input120.00 kW
Motor and drive efficiency94.000 %

Applying the formula below gives:

ResultValue
Outlet velocity pressure343.75 Pa
Fan total pressure2,843.8 Pa
Air power (total)85.312 kW
Static efficiency66.489 %
Total efficiency75.632 %

Open this example in the calculator and change any input.

Formula

\(p_v = \frac{\rho}{2}\left(\frac{Q}{A_o}\right)^2, \quad \Delta p_t = \Delta p_s + p_v, \quad \eta_t = \frac{Q\Delta p_t}{\eta_mP_{in}}\)

Variables

Symbol Meaning SI unit
\(Q\) Volume flow at fan inlet conditions m³/s
\(\Delta p_s\) Fan static pressure rise Pa
\(A_o\) Fan outlet area m²
\(\rho\) Air or gas density at the fan kg/m³
\(P_{in}\) Measured motor input W
\(\eta_m\) Motor and drive efficiency -
\(p_v\) Outlet velocity pressure Pa
\(\Delta p_t\) Fan total pressure Pa
\(P_a\) Air power (total) W
\(\eta_s\) Static efficiency -
\(\eta_t\) Total efficiency -

Method and standards

Fan definitions.

Where it is used

  • Fan performance checks.
  • Energy audits of FD and ID fans.

Common mistakes

  • Mixing inlet and outlet conditions.
  • Ignoring the motor efficiency.

Assumptions and limits

  • Incompressible; steady.
  • An efficiency above 100 % is flagged as a measurement or input error.

References

  • Fan pressure and efficiency definitions (fan total = static + outlet velocity pressure)

Questions and answers

Why is total efficiency higher than static?

Total efficiency credits the fan with the kinetic energy in its outlet air; static efficiency does not.

Which should I compare?

The same one the maker quotes; boiler fans are often quoted on total pressure.

What do the defaults represent?

An induced-draught fan moving 30 m³/s at 2.5 kPa static with 120 kW input.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.