FireCADCalc

Room Reverberation Time (Sabine) and Absorption Needed

Room reverberation time by Sabine's equation from volume and up to four surfaces with absorption coefficients, and the absorption to add.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 1,500 m³ plant roomControl room 600 m³ with ceiling tiles

Results

Sabine's equation suits fairly live rooms (average α below about 0.3); for dead rooms Eyring's form is better. Absorption coefficients vary with frequency: work band by band for design. The surface areas are not checked against the room volume: enter all the room's surfaces.

Total absorption (m² sabins)55.000m²
Reverberation time4.3909s
Extra absorption for the target106.00m²
Noise reduction from the extra absorption (dB)4.6646

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1,500 m³ plant room. The inputs, in the units selected above:

InputValue
Room volume1,500.0 m³
Area 1500.00 m²
Absorption 12.0000 %
Area 2300.00 m²
Absorption 25.0000 %
Area 3300.00 m²
Absorption 310.000 %
Area 40 m²
Absorption 470.000 %
Target reverberation time1.5000 s

Applying the formula below gives:

ResultValue
Total absorption (m² sabins)55.000 m²
Reverberation time4.3909 s
Extra absorption for the target106.00 m²
Noise reduction from the extra absorption (dB)4.6646

Open this example in the calculator and change any input.

Formula

\(A = \sum S_i\alpha_i, \quad T_{60} = \frac{0.161V}{A}, \quad \Delta A = \max\left(\frac{0.161V}{T_t} - A,\ 0\right), \quad \Delta L = 10\log_{10}\frac{A + \Delta A}{A}\)

Variables

Symbol Meaning SI unit
\(V\) Room volume m³
\(S_1\) Area 1 m²
\(\alpha_1\) Absorption 1 -
\(S_2\) Area 2 m²
\(\alpha_2\) Absorption 2 -
\(S_3\) Area 3 m²
\(\alpha_3\) Absorption 3 -
\(S_4\) Area 4 m²
\(\alpha_4\) Absorption 4 -
\(T_t\) Target reverberation time s
\(A\) Total absorption (m² sabins) m²
\(T_{60}\) Reverberation time s
\(\Delta A\) Extra absorption for the target m²
\(\Delta L\) Noise reduction from the extra absorption (dB) -

Method and standards

Sabine's equation.

Where it is used

  • Control rooms and plant rooms.
  • Workshop noise reduction.

Common mistakes

  • Using Sabine for very absorbent rooms.
  • Single-frequency α for broadband noise.

Assumptions and limits

  • Diffuse sound field; average absorption coefficient A/ΣS below about 0.3 (the page warns above it).
  • When the room is already deader than the target, ΔA is 0 and the page says so.

References

  • Sabine's equation T₆₀ = 0.161V/ΣSα (architectural acoustics)

Questions and answers

Why does absorption lower noise in a plant room?

Reverberant sound builds up from reflections; doubling the absorption lowers the reverberant level by 3 dB.

Does it help close to a machine?

Little: near the source the direct sound dominates; enclosures or barriers are needed there.

What do the defaults represent?

A 1,500 m³ concrete and steel plant room aiming for 1.5 s.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.