Solar PV String Sizing: Modules per String

Most and fewest PV modules in a string for an inverter, from module Voc and Vmp, their temperature coefficients and the coldest and hottest cell temperatures.

Process steam and utilitiesChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 550 W module, 5 °C to 70 °C, 1 100 V inverter400 W module, −5 °C to 75 °C, 600 V inverterBifacial 580 W, 10 °C to 65 °C, 1 500 V central inverter

Module

Site

Inverter

Results

Choose a string length between the fewest and the smaller of the two maxima; check string current against the inverter input current too.

Module Voc at the coldest temperature52.173V
Module Vmp at the hottest temperature34.964V
Module Vmp at the coldest temperature44.405V
Most modules per string (inverter maximum voltage)21.000
Most modules per string to stay inside the MPPT range22.000
Fewest modules per string (MPPT lowest voltage when hot)6.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 550 W module, 5 °C to 70 °C, 1 100 V inverter. The inputs, in the units selected above:

InputValue
Module open-circuit voltage at STC49.500 V
Module maximum-power voltage at STC41.500 V
Temperature coefficient of Voc, per °C-0.27000 %
Temperature coefficient of Vmp (or Pmax), per °C-0.35000 %
Coldest cell temperature (lowest site ambient at sunrise)5.0000 °C
Hottest cell temperature in operation70.000 °C
Inverter maximum DC input voltage1,100.0 V
Inverter lowest MPPT voltage200.00 V
Inverter highest MPPT voltage1,000.0 V

Applying the formula below gives:

ResultValue
Module Voc at the coldest temperature52.173 V
Module Vmp at the hottest temperature34.964 V
Module Vmp at the coldest temperature44.405 V
Most modules per string (inverter maximum voltage)21.000
Most modules per string to stay inside the MPPT range22.000
Fewest modules per string (MPPT lowest voltage when hot)6.0000

Open this example in the calculator and change any input.

Formula

\(V_{oc,cold} = V_{oc} \left[1 + \beta_{oc} (T_{min} - 25\,°\text{C})\right]\)

\(V_{mp,hot} = V_{mp} \left[1 + \beta_{mp} (T_{max} - 25\,°\text{C})\right]\)

\(N_{max} = \left\lfloor \frac{V_{max}}{V_{oc,cold}} \right\rfloor, \quad N_{MPP,max} = \left\lfloor \frac{V_{MPP,max}}{V_{mp,cold}} \right\rfloor, \quad N_{min} = \left\lceil \frac{V_{MPP,min}}{V_{mp,hot}} \right\rceil\)

Variables

Symbol Meaning SI unit
\(V_{oc}\) Module open-circuit voltage at STC V
\(V_{mp}\) Module maximum-power voltage at STC V
\(\beta_{oc}\) Temperature coefficient of Voc, per °C -
\(\beta_{mp}\) Temperature coefficient of Vmp (or Pmax), per °C -
\(T_{min}\) Coldest cell temperature (lowest site ambient at sunrise) K
\(T_{max}\) Hottest cell temperature in operation K
\(V_{max}\) Inverter maximum DC input voltage V
\(V_{MPP,min}\) Inverter lowest MPPT voltage V
\(V_{MPP,max}\) Inverter highest MPPT voltage V
\(V_{oc,cold}\) Module Voc at the coldest temperature V
\(V_{mp,hot}\) Module Vmp at the hottest temperature V
\(V_{mp,cold}\) Module Vmp at the coldest temperature V
\(N_{max}\) Most modules per string (inverter maximum voltage) -
\(N_{MPP,max}\) Most modules per string to stay inside the MPPT range -
\(N_{min}\) Fewest modules per string (MPPT lowest voltage when hot) -

Method and standards

Module voltages are corrected linearly from standard test conditions (25 °C cell) with the data-sheet coefficients. The string must stay below the inverter maximum at the coldest Voc, and inside the MPPT window at the hottest and coldest Vmp.

Where it is used

  • Designing rooftop and ground-mount PV strings.
  • Checking an inverter choice for a module.
  • Checking strings after a module change.

Common mistakes

  • Using the Pmax coefficient for Voc.
  • Using average ambient instead of record low.
  • Forgetting the string current must suit the inverter input too.

Assumptions and limits

  • Linear temperature coefficients; irradiance effects on Voc not included.
  • Cell temperature at the hottest case estimated by you.
  • Use the Vmp coefficient where the data sheet gives it. The Pmax coefficient is usually larger in magnitude: it makes N_min conservative but N_MPP,max less so.
  • The page warns when even one module exceeds the inverter maximum, and when the inverter maximum is below its MPPT high voltage.

References

  • IEC 61215 / IEC 60904-3 standard test conditions
  • Module temperature coefficients from the data sheet

Questions and answers

How many 49.5 V modules fit a 1 100 V inverter?

At 5 °C the module Voc rises to 52.2 V, so 21 modules give 1 096 V. More would exceed the inverter maximum on a cold morning.

What sets the fewest?

The hot Vmp: at 70 °C the module Vmp falls to 35.0 V, so a 200 V MPPT minimum needs at least 6 modules.

Which temperature should I use for the coldest case?

The lowest site ambient at sunrise, when the modules are cold but already lit; cell temperature then equals ambient.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.