Worked example
Example: 1 MWp, 5.2 kWh/m²/day, PR 0.78, 365 days. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Plant rating (DC, at STC) | 1,000.0 kW |
| Irradiation on the modules (kWh/m² per day = peak sun hours) | 5.2000 - |
| Performance ratio | 78.000 % |
| Days in the period | 365.00 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy per day | 4,056.0 kWh |
| Energy in the period | 1,480.4 MWh |
| Specific yield (kWh per kWp) | 1,480.4 |
| Capacity utilisation factor (on DC kWp) | 16.900 % |
Open this example in the calculator and change any input.
Formula
\(E_d = P_{pk}\,H\,PR \qquad E = E_d\,d \qquad Y_f = H\,PR\,d \qquad CUF = \frac{H\,PR}{24}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_{pk}\) | DC rating at STC | W |
| \(H\) | daily irradiation on the modules (peak sun hours) | kWh/m² per day |
| \(PR\) | performance ratio | – |
| \(d\) | days | – |
| \(E_d\) | energy per day | J |
| \(E\) | energy in the period | J |
| \(Y_f\) | specific yield | kWh/kWp |
| \(CUF\) | capacity utilisation factor, on the DC kWp rating | – |
Method and standards
Reference yield (irradiation over 1 kW/m²) times performance ratio, as defined in IEC 61724-1.
Where it is used
- Captive solar plant feasibility.
- Monitoring plant performance.
- Carbon accounting.
Common mistakes
- Using horizontal irradiation for tilted modules.
- Taking PR above 0.85 for warm climates.
- Forgetting degradation over the years.
Assumptions and limits
- Yearly mean conditions; degradation and curtailment not included.
- CUF is on the DC (kWp) rating; Indian plant reports often quote it on the AC (inverter) capacity, which is higher by the DC/AC ratio.
References
- IEC 61724-1 (performance ratio definition)
Questions and answers
How much does a 1 MWp plant make in a year?
With 5.2 kWh/m²/day on the modules and PR 0.78: 14.6 MWh a day, 5330 MWh a year, 1480 kWh/kWp and a CUF of 16.9 %.
What is the performance ratio?
Actual energy over the energy the array would give at STC efficiency; it covers temperature, soiling, wiring and inverter losses.
Is CUF on DC or AC rating?
Here on DC kWp; on AC rating it is higher by the DC/AC ratio.