Worked example
Example: 400 kWh/day, 5 h, PR 0.78, 550 Wp modules 2.58 m², GCR 0.5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Energy needed per day | 400.00 kWh |
| Irradiation on the modules (kWh/m² per day = peak sun hours) | 5.0000 - |
| Performance ratio | 78.000 % |
| Module rating (Wp) | 550.00 W |
| Module area | 2.5800 m² |
| Ground (roof) coverage ratio | 50.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Array rating needed (DC) | 102.56 kW |
| Number of modules (whole) | 187.00 |
| Array rating with whole modules | 102.85 kW |
| Module area in total | 482.46 m² |
| Roof or land area | 964.92 m² |
Open this example in the calculator and change any input.
Formula
\(P_{pk} = \frac{E_d}{H\,PR} \qquad N = \left\lceil \frac{P_{pk}}{P_m} \right\rceil \qquad P_{act} = N P_m \qquad A_l = \frac{N A_m}{GCR}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E_d\) | energy needed per day (AC at the meter if PR includes inverter and transformer losses) | J |
| \(H\) | peak sun hours | h/day |
| \(PR\) | performance ratio | – |
| \(P_m\) | module rating | W |
| \(A_m\) | module area | m² |
| \(GCR\) | ground coverage ratio | – |
| \(P_{pk}\) | array rating needed | W |
| \(N\) | number of modules | – |
| \(P_{act}\) | rating with whole modules | W |
| \(A_m N\) | module area in total | m² |
| \(A_l\) | roof or land area | m² |
Method and standards
Inverse of the reference-yield relation of IEC 61724-1, rounded up to whole modules.
Where it is used
- Rooftop solar on plant buildings.
- Solar for pumping and lighting.
- Land estimates for ground-mounted plants.
Common mistakes
- Using the module's area efficiency instead of PR.
- Ignoring shading from stacks and structures.
- Sizing on yearly mean for off-grid loads.
Assumptions and limits
- Yearly mean irradiation; string and inverter design separate.
- E_d is AC energy only when the performance ratio includes inverter and transformer losses.
- Module rating and area are independent inputs; the page warns when they imply an efficiency outside 5–30 % at 1000 W/m².
References
- IEC 61724-1 (performance ratio definition)
Questions and answers
What array covers 400 kWh a day?
At 5 peak sun hours and PR 0.78: 102.6 kWp, or 187 modules of 550 Wp (102.9 kWp) on about 965 m² at a coverage ratio of 0.5.
Why the coverage ratio?
Tilted rows need space between them to avoid shading; flush roof mounting can use most of the area.
Is this enough for off-grid?
No. Off-grid systems are sized on the worst month and need batteries.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.