FireCADCalc

Neutral Current from Triplen Harmonics

Neutral current in a three-phase four-wire system with balanced single-phase non-linear loads, from phase current and its 3rd, 9th and 15th harmonic content.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Office loads, 70 % 3rdLED lighting, 30 % 3rd

Results

Balanced loads: fundamental and non-triplen harmonics cancel in the neutral, triplens add arithmetically (×3). Other harmonics in the phase current are not included here.

Phase rms current (triplens and fundamental)123.09A
Neutral rms current215.29A
Neutral-to-phase ratio1.7491

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Office loads, 70 % 3rd. The inputs, in the units selected above:

InputValue
Fundamental phase current100.00 A
3rd harmonic share70.000 %
9th harmonic share15.000 %
15th harmonic share5.0000 %

Applying the formula below gives:

ResultValue
Phase rms current (triplens and fundamental)123.09 A
Neutral rms current215.29 A
Neutral-to-phase ratio1.7491

Open this example in the calculator and change any input.

Formula

\(I_N = 3\sqrt{I_3^2 + I_9^2 + I_{15}^2}, \quad I_{ph} = \sqrt{I_1^2 + I_3^2 + I_9^2 + I_{15}^2}\)

Variables

Symbol Meaning SI unit
\(I_1\) Fundamental phase current A
\(I_3/I_1\) 3rd harmonic share -
\(I_9/I_1\) 9th harmonic share -
\(I_{15}/I_1\) 15th harmonic share -
\(I_{ph}\) Phase rms current (triplens and fundamental) A
\(I_N\) Neutral rms current A
\(I_N/I_{ph}\) Neutral-to-phase ratio -

Method and standards

Triplen addition.

Where it is used

  • Neutral conductor sizing.
  • Commercial and IT installations.

Common mistakes

  • Sizing neutral at half phase for non-linear loads.
  • Assuming unbalance is the cause.

Assumptions and limits

  • The phase rms current includes only the fundamental and the triplen harmonics entered. Real rectifier currents also carry 5th, 7th, 11th … harmonics, which raise the phase current but cancel in the neutral, so the neutral-to-phase ratio shown is an upper value.

  • Balanced single-phase loads.

References

  • Triplen harmonic addition in the neutral
  • I_N = 3√ΣI_3k² (power quality definitions)

Questions and answers

Why can neutral current exceed phase current?

Triplen harmonics are in phase in all three phases and add in the neutral instead of cancelling.

Which loads cause it?

Single-phase rectifier loads: computers, LED drivers, UPS inputs; 3rd harmonic can reach 70–80 % of fundamental.

What do the defaults represent?

Office loads with 70 % third harmonic on 100 A phases.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.