FireCADCalc

Tank Vent Flow from Filling and Emptying (Displacement)

Air out of a tank vent while filling and air in while emptying, from the liquid pumping rates, and the velocity in the vent pipe (liquid displacement only).

Refinery and petrochemicalChemical and fertiliserFood, dairy and textile

Inputs

Examples: DN80 ventEmptying governs

Results

Displacement only: thermal breathing, flashing and fire cases are set by the tank venting standard you follow.

Air out while filling30.000m³/h
Air in while emptying150.00m³/h
Highest vent velocity5.0693m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: DN80 vent. The inputs, in the units selected above:

InputValue
Filling rate120.00 m³/h
Emptying rate80.000 m³/h
Vent pipe bore77.900 mm

Applying the formula below gives:

ResultValue
Air out while filling120.00 m³/h
Air in while emptying80.000 m³/h
Highest vent velocity6.9938 m/s

Open this example in the calculator and change any input.

Formula

\(\dot V_{out} = \dot V_f, \quad \dot V_{in} = \dot V_e, \quad v = \frac{\max(\dot V)}{\pi D^2/4}\)

Variables

Symbol Meaning SI unit
\(\dot V_f\) Filling rate m³/s
\(\dot V_e\) Emptying rate m³/s
\(D\) Vent pipe bore m
\(\dot V_{out}\) Air out while filling m³/s
\(\dot V_{in}\) Air in while emptying m³/s
\(v\) Highest vent velocity m/s

Method and standards

Displacement.

Where it is used

  • Fuel oil, acid and DM water tanks.
  • Day tanks.

Common mistakes

  • Ignoring thermal breathing.
  • Flame arrester pressure drop.

Assumptions and limits

  • Displacement only: thermal in- and out-breathing, flashing and fire cases are excluded.
  • No vent pressure drop is computed, so the velocity alone does not confirm the vent size; check the pressure drop against the tank's design pressure and vacuum.

References

  • Liquid displacement: air flow equals the liquid volume flow

Questions and answers

Filling at 120 m³/h through a DN80 vent?

120 m³/h of air out at about 7 m/s.

Is that the whole vent duty?

No: add thermal breathing and any vapour flashing per your venting standard.

Why size for emptying?

Too small a vent while pumping out can pull a vacuum and collapse the tank.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.