Worked example
Example: DN80 vent. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Filling rate | 120.00 m³/h |
| Emptying rate | 80.000 m³/h |
| Vent pipe bore | 77.900 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air out while filling | 120.00 m³/h |
| Air in while emptying | 80.000 m³/h |
| Highest vent velocity | 6.9938 m/s |
Open this example in the calculator and change any input.
Formula
\(\dot V_{out} = \dot V_f, \quad \dot V_{in} = \dot V_e, \quad v = \frac{\max(\dot V)}{\pi D^2/4}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_f\) | Filling rate | m³/s |
| \(\dot V_e\) | Emptying rate | m³/s |
| \(D\) | Vent pipe bore | m |
| \(\dot V_{out}\) | Air out while filling | m³/s |
| \(\dot V_{in}\) | Air in while emptying | m³/s |
| \(v\) | Highest vent velocity | m/s |
Method and standards
Displacement.
Where it is used
- Fuel oil, acid and DM water tanks.
- Day tanks.
Common mistakes
- Ignoring thermal breathing.
- Flame arrester pressure drop.
Assumptions and limits
- Displacement only: thermal in- and out-breathing, flashing and fire cases are excluded.
- No vent pressure drop is computed, so the velocity alone does not confirm the vent size; check the pressure drop against the tank's design pressure and vacuum.
References
- Liquid displacement: air flow equals the liquid volume flow
Questions and answers
Filling at 120 m³/h through a DN80 vent?
120 m³/h of air out at about 7 m/s.
Is that the whole vent duty?
No: add thermal breathing and any vapour flashing per your venting standard.
Why size for emptying?
Too small a vent while pumping out can pull a vacuum and collapse the tank.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.