Worked example
Example: Illustrative 50 vans, 22 kW chargers, 8 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Vehicles | 50.000 - |
| Distance per vehicle per day | 180.00 km |
| Consumption at the wheels from the battery | 220.00 Wh/km |
| Charging efficiency (grid to battery) | 90.000 % |
| Charging window | 8.0000 h |
| Charger power | 22.000 kW |
| Diversity factor (share charging at once) | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Grid energy per day | 2.2000 MWh |
| Average power over the window | 275.00 kW |
| Chargers needed (each runs the whole window) | 13.000 |
| Peak demand with diversity | 275.00 kW |
Open this example in the calculator and change any input.
Formula
\(E = \frac{Nde}{\eta_c}, \quad n_c = \left\lceil\frac{E}{P_ct_w}\right\rceil, \quad P_{pk} = n_cP_ck_d\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(N\) | Vehicles | - |
| \(d\) | Distance per vehicle per day | m |
| \(e\) | Consumption at the wheels from the battery | J/m |
| \(\eta_c\) | Charging efficiency (grid to battery) | - |
| \(t_w\) | Charging window | s |
| \(P_c\) | Charger power | W |
| \(k_d\) | Diversity factor (share charging at once) | - |
| \(E\) | Grid energy per day | J |
| \(\bar P\) | Average power over the window | W |
| \(n_c\) | Chargers needed (each runs the whole window) | - |
| \(P_{pk}\) | Peak demand with diversity | W |
Method and standards
Fleet charging.
Where it is used
- Depot electrification planning.
- Grid connection applications.
Common mistakes
- Forgetting charging losses.
- Assuming all chargers run at full power all night.
Assumptions and limits
- Daily average duty; one charging window.
References
- Fleet charging energy balance
Questions and answers
How much power does a depot need?
Total daily energy over the charging window sets the average; diversity and smart charging decide how far the peak rises above it.
Why use diversity?
Not every vehicle charges at full power at the same time; batteries arrive at different states of charge and taper near full.
What do the defaults represent?
An illustrative fleet of 50 vans, 180 km a day each at 220 Wh/km, 90 % charging efficiency, an 8-hour overnight window and 22 kW chargers with 80 % diversity.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004)