FireCADCalc

Vapour Displaced When Filling a Tank

Mass of product vapour pushed out of a fixed-roof tank by filling, from the volume filled, vapour pressure, molar mass and temperature, per fill and per year.

Inputs

Examples: Illustrative 1000 m3 gasoline-like fillsWith 95 % vapour recoveryToluene 200 m3 weekly

Accepted: 0.01 to 1,000,000 m³
Accepted: 0.01 to 200 kPa
Accepted: 2 to 300 kg/kmol
Accepted: -43.15 to 126.85 °C
Accepted: 5 to 100 %
Accepted: 0 to 10,000
Accepted: 0 to 100 %

Results

Displaced gas volume equals the liquid volume filled; it carries vapour at K_s·p_v partial pressure (ideal gas). Breathing losses from daily temperature swings come on top; emission inventories use the regulator's method and factors.

Vapour concentration in the displaced gas0.63898kg/m³
Vapour lost per fill31.949kg
Vapour lost per year0.95847t

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 1000 m3 gasoline-like fills. The inputs, in the units selected above:

InputValue
Liquid volume filled1,000.0 m³
True vapour pressure at storage temperature30.000 kPa
Vapour molar mass66.000 kg/kmol
Vapour space temperature25.000 °C
Vapour saturation factor80.000 %
Fills per year30.000 -
Vapour recovery efficiency0 %

Applying the formula below gives:

ResultValue
Vapour concentration in the displaced gas0.63898 kg/m³
Vapour lost per fill638.98 kg
Vapour lost per year19.169 t

Open this example in the calculator and change any input.

Formula

\(c_v = \frac{K_sp_vM}{RT}, \quad m = V_fc_v(1 - \eta_r)\)

Variables

Symbol Meaning SI unit
\(V_f\) Liquid volume filled m³
\(p_v\) True vapour pressure at storage temperature Pa
\(M\) Vapour molar mass kg/kmol
\(T\) Vapour space temperature K
\(K_s\) Vapour saturation factor -
\(N\) Fills per year -
\(\eta_r\) Vapour recovery efficiency -
\(c_v\) Vapour concentration in the displaced gas kg/m³
\(m_1\) Vapour lost per fill kg
\(m_y\) Vapour lost per year kg

Method and standards

Displacement loss.

Where it is used

  • Emission estimates and vapour recovery business cases.
  • Product loss accounting.

Common mistakes

  • Using Reid vapour pressure as true vapour pressure.
  • Forgetting breathing losses.

Assumptions and limits

  • Ideal gas; uniform vapour concentration.

References

  • Ideal-gas vapour content of displaced tank gas

Questions and answers

Why do tanks lose product when filled?

Incoming liquid pushes out the gas above it, which is nearly saturated with product vapour.

How can losses be cut?

Vapour balancing or recovery units, internal floating roofs, and filling at lower temperatures.

What do the defaults represent?

An illustrative fixed-roof tank receiving 1,000 m³ of light gasoline-like product (30 kPa vapour pressure, M = 66) 30 times a year at 25 °C, vapour 80 % saturated.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Perry's Chemical Engineers' Handbook (McGraw-Hill)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.