Worked example
Example: FD fan at 40 °C and 600 m to standard air 1.2 kg/m³. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Volume flow at the fan inlet | 72,000 m³/h |
| Fan pressure at site conditions | 305.91 mmWC |
| Shaft power at site conditions | 75.000 kW |
| Gas temperature at the fan inlet | 40.000 °C |
| Molar mass of the gas | 28.966 kg/kmol |
| Site pressure from | Altitude (ISO 2533 standard atmosphere) |
| Site altitude above sea level | 600.00 m |
| Barometric pressure at the site (absolute) | 1.0132 bar |
| Standard (test) density | 1.2000 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fan pressure at standard density | 349.84 mmWC |
| Shaft power at standard density | 85.769 kW |
| Density ratio standard / site | 1.1436 |
| Gas density at site conditions | 1.0493 kg/m³ |
| Mass flow of standard air at the same volume | 86,400 kg/h |
| Barometric pressure used | 0.94322 bar |
Open this example in the calculator and change any input.
Formula
\(\rho = \frac{p\,M}{R\,T} \qquad k = \frac{\rho_0}{\rho} \qquad \Delta p_0 = k\,\Delta p \qquad P_0 = k\,P \qquad \dot m_0 = \rho_0\,\dot V\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | volume flow at the fan inlet | m³/s |
| \(\Delta p\) | fan pressure at site conditions | Pa |
| \(P\) | shaft power at site conditions | W |
| \(T\) | gas temperature at the fan inlet | K |
| \(M\) | molar mass of the gas | kg/kmol |
| \(\text{site}\) | site pressure from altitude or entered | – |
| \(z\) | site altitude | m |
| \(p_s\) | barometric pressure entered | Pa |
| \(\rho_0\) | standard (test) density | kg/m³ |
| \(\Delta p_0\) | fan pressure at standard density | Pa |
| \(P_0\) | shaft power at standard density | W |
| \(\rho_0/\rho\) | density ratio | – |
| \(\rho\) | gas density at site | kg/m³ |
| \(\dot m_0\) | mass flow of standard air at the same volume | kg/s |
| \(p\) | barometric pressure used | Pa |
| \(R\) | universal gas constant | J/(mol·K) |
Method and standards
Fan laws of AMCA Publication 99 at constant speed and size: pressure and power in proportion to density, volume flow unchanged. Standard air of 1.2 kg/m³ as in AMCA 210; site pressure from ISO 2533; ideal-gas density.
Where it is used
- Correcting fan ratings to site gas temperature and altitude.
- Choosing fan motors for cold start.
- Comparing fan tests at different conditions.
Common mistakes
- Forgetting the cold-start case for hot-gas fans.
- Using sea-level density at a hill site.
- Correcting volume flow, which does not change with density for a given speed.
Assumptions and limits
- Same fan, same speed, same point of rating.
- Inlet suction is neglected in the density; for an ID fan with a large suction, enter the inlet absolute pressure as the barometric pressure.
- Compressibility neglected.
References
- AMCA 99 (fan laws)
- AMCA 210 (standard air 1.2 kg/m³)
- ISO 2533 (site pressure)
Questions and answers
How do I read a fan catalogue for hot gas?
Catalogues are for standard air (1.2 kg/m³). At the same speed and volume flow, pressure and power scale with density. An ID fan duty of 2.5 kPa on flue gas at 150 °C is 3.47 kPa in standard air: look it up in the catalogue at that pressure.
Does the volume flow change?
No. A fan at a given speed moves the same volume whatever the density; the mass flow changes.
What about altitude?
The site pressure lowers the density in the same way: at 600 m and 40 °C air is 1.05 kg/m³, so a catalogue fan delivers 12.5 % less pressure at site.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.