Ground-Source Heat Pump Borehole Length

Ground heat load, total borehole length and number of boreholes for a ground-source heat pump from heating capacity, COP and a specific heat extraction rate.

Food, dairy and textile

Inputs

Examples: Illustrative 12 kW house, COP 4, 50 W/mOffice 120 kW, COP 4.5, 55 W/m, 150 mDry ground 8 kW, 25 W/m

Accepted: 0.1 to 100,000 kW
Accepted: 1.5 to 8
Accepted: 5 to 150 W/m
Accepted: 10 to 500 m
Accepted: 0 to 8,760 h

Results

Q_g = Q_h(1 − 1/COP); L = Q_g/q'. Rule-of-thumb extraction rates are about 20–30 W/m in dry sediments, 50–60 W/m in water-saturated rock and up to 80 W/m in good crystalline rock for about 1,800–2,400 full-load hours. Large or unbalanced systems need a thermal response test and a simulation.

Heat extracted from the ground9.0000kW
Total borehole length180.00m
Number of boreholes2.0000
Heat extracted per year16.200MWh
Annual extraction per metre (kWh/m)90.000
Compressor electrical power3.0000kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 12 kW house, COP 4, 50 W/m. The inputs, in the units selected above:

InputValue
Heat pump heating capacity12.000 kW
Coefficient of performance4.0000 -
Specific heat extraction rate of the ground (W per m of borehole)50.000 W/m
Maximum depth per borehole100.00 m
Full-load hours per year1,800.0 h

Applying the formula below gives:

ResultValue
Heat extracted from the ground9.0000 kW
Total borehole length180.00 m
Number of boreholes2.0000
Heat extracted per year16.200 MWh
Annual extraction per metre (kWh/m)90.000
Compressor electrical power3.0000 kW

Open this example in the calculator and change any input.

Formula

\(\dot Q_g = \dot Q_h\left(1 - \frac{1}{COP}\right), \quad L = \frac{\dot Q_g}{q'}, \quad n = \left\lceil\frac{L}{H}\right\rceil\)

Variables

Symbol Meaning SI unit
\(\dot Q_h\) Heat pump heating capacity W
\(COP\) Coefficient of performance -
\(q'\) Specific heat extraction rate of the ground (W per m of borehole) W/m
\(H\) Maximum depth per borehole m
\(t_{fl}\) Full-load hours per year s
\(\dot Q_g\) Heat extracted from the ground W
\(L\) Total borehole length m
\(n\) Number of boreholes -
\(E_g\) Heat extracted per year J
\(E_g/L\) Annual extraction per metre (kWh/m) -
\(P_{el}\) Compressor electrical power W

Method and standards

Borehole field sizing.

Where it is used

  • Small ground-source heat pump design.
  • Feasibility of geothermal heating.

Common mistakes

  • Sizing on the heating output instead of the ground load.
  • Using high W/m values for dry ground.

Assumptions and limits

  • Heating-dominated load; rule-of-thumb extraction rate.

References

  • Specific heat-extraction sizing of borehole heat exchangers

Questions and answers

Why does the ground supply less than the heating output?

The heat pump's electricity also becomes heat, so the ground supplies only Q(1 − 1/COP), three-quarters at a COP of 4.

How deep are boreholes?

Usually 80–200 m, spaced at least 6–10 m apart so they do not cool each other.

What do the defaults represent?

An illustrative 12 kW house heat pump at COP 4 in rock giving 50 W/m, boreholes up to 100 m, 1,800 full-load hours.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Kothari, Singal and Ranjan, Renewable Energy Sources and Emerging Technologies, 2nd ed. (PHI, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.