Worked example
Example: 600 kWp on five 100 kW inverters. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Array rating | 600.00 kW |
| Rating of one inverter | 100.00 kW |
| Number of inverters | 5.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| DC/AC ratio | 1.2000 |
| DC power per inverter | 120.00 kW |
| Oversizing of the array over the inverters | 20.000 % |
| Total inverter rating | 500.00 kW |
Open this example in the calculator and change any input.
Formula
\(R = \frac{P_{dc}}{n\, P_{ac}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_{dc}\) | Array rating | W |
| \(P_{ac}\) | Rating of one inverter | W |
| \(n\) | Number of inverters | - |
| \(R\) | DC/AC ratio | - |
| \(P_{dc,1}\) | DC power per inverter | W |
| \(o\) | Oversizing of the array over the inverters | - |
| \(P_{ac,t}\) | Total inverter rating | W |
Method and standards
Ratio of ratings.
Where it is used
- Plant design and inverter selection.
Common mistakes
- Exceeding the maker's DC limits.
Assumptions and limits
- Ratings only; no energy simulation.
References
- Definition: array STC power / inverter AC rating
Questions and answers
What is the ratio of 600 kWp on five 100 kW inverters?
1.2: the array is 20 % larger than the inverters.
Is that allowed?
Usually; check the inverter's maximum DC power, voltage and current.
Why oversize?
Modules rarely reach their rated power in the field.