Lighting Design by the Lumen Method

Number of light fittings for a required illuminance by the lumen method, from area, lumens per fitting, utilisation factor and maintenance factor.

BoilerElectrician and wireman licence examinations

Inputs

Examples: Boiler house floor 150 lux, 600 m², 20 000 lm fittings, UF 0.6, MF 0.7Control room 500 lux, 120 m², 4000 lm, 0.65, 0.8Coal yard 30 lux, 5000 m², 30 000 lm, 0.5, 0.65

From the fitting's photometric tables for the room index and reflectances.
Allows for dirt and lumen depreciation; lower for dusty boiler houses and coal yards.

Results

Space the fittings no wider than their spacing-to-height ratio allows, or the illuminance will be uneven.

Fittings needed (whole number)16.000
Average illuminance with that number (lux)31.200
Fittings, exact15.385

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Boiler house floor 150 lux, 600 m², 20 000 lm fittings, UF 0.6, MF 0.7. The inputs, in the units selected above:

InputValue
Required average illuminance (lux)150.00 -
Area to light600.00 m²
Lumens per fitting20,000 -
Utilisation factor60.000 %
Maintenance factor70.000 %

Applying the formula below gives:

ResultValue
Fittings needed (whole number)11.000
Average illuminance with that number (lux)154.00
Fittings, exact10.714

Open this example in the calculator and change any input.

Formula

\(N = \frac{E\,A}{\Phi\,UF\,MF} \qquad E_{act} = \frac{\lceil N \rceil\,\Phi\,UF\,MF}{A}\)

Variables

Symbol Meaning SI unit
\(E\) required illuminance lux
\(A\) area m²
\(\Phi\) lumens per fitting lm
\(UF\) utilisation factor –
\(MF\) maintenance factor –
\(N\) fittings needed –
\(E_{act}\) illuminance achieved lux
\(N_c\) fittings, exact –

Method and standards

Lumen method for average illuminance over a work plane.

Where it is used

  • Lighting boiler houses, turbine halls, control rooms and yards.
  • Retrofitting with LED fittings.
  • Quick checks of lighting layouts.

Common mistakes

  • Using lamp lumens instead of fitting lumens.
  • Ignoring spacing limits, which cause dark patches.
  • Using a high maintenance factor in dusty areas.

Assumptions and limits

  • Average illuminance; uniform layout.

References

  • Lumen method of average illuminance

Questions and answers

How many fittings light a boiler house?

150 lux over 600 m² with 20 000-lumen fittings, UF 0.6 and MF 0.7 needs 10.7, so 11 fittings, giving 154 lux.

What lux levels are used?

Lighting standards give values by task: plant floors and walkways need much less than control rooms. Use the standard that applies to your site.

Why the maintenance factor?

Lamps lose output and fittings get dirty; dusty boiler houses and coal yards need lower factors.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators