Worked example
Example: Boiler house floor 150 lux, 600 m², 20 000 lm fittings, UF 0.6, MF 0.7. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Required average illuminance (lux) | 150.00 - |
| Area to light | 600.00 m² |
| Lumens per fitting | 20,000 - |
| Utilisation factor | 60.000 % |
| Maintenance factor | 70.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fittings needed (whole number) | 11.000 |
| Average illuminance with that number (lux) | 154.00 |
| Fittings, exact | 10.714 |
Open this example in the calculator and change any input.
Formula
\(N = \frac{E\,A}{\Phi\,UF\,MF} \qquad E_{act} = \frac{\lceil N \rceil\,\Phi\,UF\,MF}{A}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | required illuminance | lux |
| \(A\) | area | m² |
| \(\Phi\) | lumens per fitting | lm |
| \(UF\) | utilisation factor | – |
| \(MF\) | maintenance factor | – |
| \(N\) | fittings needed | – |
| \(E_{act}\) | illuminance achieved | lux |
| \(N_c\) | fittings, exact | – |
Method and standards
Lumen method for average illuminance over a work plane.
Where it is used
- Lighting boiler houses, turbine halls, control rooms and yards.
- Retrofitting with LED fittings.
- Quick checks of lighting layouts.
Common mistakes
- Using lamp lumens instead of fitting lumens.
- Ignoring spacing limits, which cause dark patches.
- Using a high maintenance factor in dusty areas.
Assumptions and limits
- Average illuminance; uniform layout.
References
- Lumen method of average illuminance
Questions and answers
How many fittings light a boiler house?
150 lux over 600 m² with 20 000-lumen fittings, UF 0.6 and MF 0.7 needs 10.7, so 11 fittings, giving 154 lux.
What lux levels are used?
Lighting standards give values by task: plant floors and walkways need much less than control rooms. Use the standard that applies to your site.
Why the maintenance factor?
Lamps lose output and fittings get dirty; dusty boiler houses and coal yards need lower factors.