UPS Battery Ah Sizing for Backup Time

Battery capacity in ampere-hours for a UPS or DC system from the load, backup time, DC voltage, inverter efficiency, depth of discharge and ageing and temperature factors.

Thermal power plantElectric motor

Inputs

Examples: DCS UPS 10 kW, 30 min, 220 V DC, 92 %, 80 % DoD, ageing 1.25Boiler control 3 kW, 60 min, 110 V, 90 %, 80 %, 1.25, cold room 1.1Emergency lighting 1.5 kW, 90 min, 48 V, 88 %, 70 %, 1.2DCS UPS 10 kW, 30 min, sized at the 1.75 V/cell end voltage

Above 1 for batteries kept in a cold room; from the battery maker.
1 sizes on the nominal voltage. A constant-power load draws most current at the end of discharge: for lead-acid ending at 1.75 V per 2 V cell enter 0.875 for a conservative size.

Results

Current taken at the nominal voltage. Under constant power the current rises as the voltage falls; at the end of discharge (about 1.75 V per lead-acid cell) it is about 14 % higher, so this Ah figure can be 10–15 % low. Enter a voltage share of 0.875 to size on the end voltage.

Capacity at the backup-time discharge rate: high discharge rates give less than the 10-hour rated capacity; check the battery maker's discharge tables.

Battery capacity needed38.599Ah
Average battery discharge current49.407A
Energy drawn from the battery5.4348kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: DCS UPS 10 kW, 30 min, 220 V DC, 92 %, 80 % DoD, ageing 1.25. The inputs, in the units selected above:

InputValue
Load on the UPS (active power)10.000 kW
Backup time30.000 min
Nominal battery (DC bus) voltage220.00 V
Inverter efficiency92.000 %
Allowed depth of discharge80.000 %
Ageing factor1.2500 -
Temperature correction factor1.0000 -
Battery voltage for the current, as a share of nominal100.00 %

Applying the formula below gives:

ResultValue
Battery capacity needed38.599 Ah
Average battery discharge current49.407 A
Energy drawn from the battery5.4348 kWh

Open this example in the calculator and change any input.

Formula

\(I_{dc} = \frac{P}{k_v V_{dc}\,\eta_i} \qquad C = \frac{I_{dc}\,t\,k_a\,k_t}{DoD} \qquad E = \frac{P\,t}{\eta_i}\)

Variables

Symbol Meaning SI unit
\(P\) load W
\(t\) backup time s
\(V_{dc}\) DC bus voltage V
\(\eta_i\) inverter efficiency –
\(DoD\) depth of discharge –
\(k_a\) ageing factor –
\(k_t\) temperature factor –
\(k_v\) battery voltage for the current as a share of nominal (1 = nominal) –
\(C\) capacity needed (shown in Ah) C
\(I_{dc}\) discharge current A
\(E\) energy drawn J

Method and standards

Constant-power discharge converted to a constant current at nominal voltage, with ageing, temperature and depth-of-discharge factors.

Where it is used

  • UPS for DCS, boiler controls and emergency lighting.
  • DC systems for switchgear tripping.
  • Checking backup time of existing batteries.

Common mistakes

  • Using kVA instead of kW of the load.
  • Ignoring the discharge rate's effect on capacity.
  • Forgetting end-of-life capacity.

Assumptions and limits

  • Constant power; factors as entered.
  • With k_v = 1 the current is taken at the nominal voltage, which understates it: under constant power the current rises as the battery voltage falls, to about 14 % above the nominal-voltage value at a lead-acid end voltage of 1.75 V per cell. k_v = 0.875 sizes on the end voltage (conservative); a value near 0.95 approximates the average discharge voltage.
  • A load of zero is rejected.

References

  • Energy balance of the battery discharge with correction factors

Questions and answers

What battery does a 10 kW UPS need for 30 minutes?

On a 220 V DC bus with a 92 % inverter the battery gives 49 A; with 80 % depth of discharge and an ageing factor of 1.25 it needs about 39 Ah at the half-hour rate.

Why the ageing factor?

Batteries lose capacity with age; sizing with 1.25 keeps the backup time until capacity falls to 80 %.

Is the Ah the 10-hour rating?

No: at short backup times the battery gives fewer Ah than its 10-hour rating; pick the battery from the maker's discharge tables.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.