Worked example
Example: DCS UPS 10 kW, 30 min, 220 V DC, 92 %, 80 % DoD, ageing 1.25. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Load on the UPS (active power) | 10.000 kW |
| Backup time | 30.000 min |
| Nominal battery (DC bus) voltage | 220.00 V |
| Inverter efficiency | 92.000 % |
| Allowed depth of discharge | 80.000 % |
| Ageing factor | 1.2500 - |
| Temperature correction factor | 1.0000 - |
| Battery voltage for the current, as a share of nominal | 100.00 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Battery capacity needed | 38.599 Ah |
| Average battery discharge current | 49.407 A |
| Energy drawn from the battery | 5.4348 kWh |
Open this example in the calculator and change any input.
Formula
\(I_{dc} = \frac{P}{k_v V_{dc}\,\eta_i} \qquad C = \frac{I_{dc}\,t\,k_a\,k_t}{DoD} \qquad E = \frac{P\,t}{\eta_i}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | load | W |
| \(t\) | backup time | s |
| \(V_{dc}\) | DC bus voltage | V |
| \(\eta_i\) | inverter efficiency | – |
| \(DoD\) | depth of discharge | – |
| \(k_a\) | ageing factor | – |
| \(k_t\) | temperature factor | – |
| \(k_v\) | battery voltage for the current as a share of nominal (1 = nominal) | – |
| \(C\) | capacity needed (shown in Ah) | C |
| \(I_{dc}\) | discharge current | A |
| \(E\) | energy drawn | J |
Method and standards
Constant-power discharge converted to a constant current at nominal voltage, with ageing, temperature and depth-of-discharge factors.
Where it is used
- UPS for DCS, boiler controls and emergency lighting.
- DC systems for switchgear tripping.
- Checking backup time of existing batteries.
Common mistakes
- Using kVA instead of kW of the load.
- Ignoring the discharge rate's effect on capacity.
- Forgetting end-of-life capacity.
Assumptions and limits
- Constant power; factors as entered.
- With k_v = 1 the current is taken at the nominal voltage, which understates it: under constant power the current rises as the battery voltage falls, to about 14 % above the nominal-voltage value at a lead-acid end voltage of 1.75 V per cell. k_v = 0.875 sizes on the end voltage (conservative); a value near 0.95 approximates the average discharge voltage.
- A load of zero is rejected.
References
- Energy balance of the battery discharge with correction factors
Questions and answers
What battery does a 10 kW UPS need for 30 minutes?
On a 220 V DC bus with a 92 % inverter the battery gives 49 A; with 80 % depth of discharge and an ageing factor of 1.25 it needs about 39 Ah at the half-hour rate.
Why the ageing factor?
Batteries lose capacity with age; sizing with 1.25 keeps the backup time until capacity falls to 80 %.
Is the Ah the 10-hour rating?
No: at short backup times the battery gives fewer Ah than its 10-hour rating; pick the battery from the maker's discharge tables.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.