Worked example
Example: 15,000 lm every 30 m, 8 m road. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Luminous flux per luminaire (lm) | 15,000 - |
| Coefficient of utilisation | 40.000 % |
| Maintenance factor | 80.000 % |
| Road width | 8.0000 m |
| Pole spacing | 30.000 m |
| Arrangement | Single-sided or staggered (one luminaire per spacing) |
| Target average illuminance | 15.000 lx |
Applying the formula below gives:
| Result | Value |
|---|---|
| Average illuminance | 20.000 lx |
| Spacing for the target | 40.000 m |
| Spacing for the target per road width (not S/h: compare S with the mounting height separately) | 5.0000 |
Open this example in the calculator and change any input.
Formula
\(E_{avg} = \frac{n\Phi\,CU\,MF}{WS}, \quad S_{req} = \frac{n\Phi\,CU\,MF}{WE_t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Phi\) | Luminous flux per luminaire (lm) | - |
| \(CU\) | Coefficient of utilisation | - |
| \(MF\) | Maintenance factor | - |
| \(W\) | Road width | m |
| \(S\) | Pole spacing | m |
| \(\text{arrangement}\) | Arrangement | - |
| \(E_t\) | Target average illuminance | lx |
| \(E_{avg}\) | Average illuminance | lx |
| \(S_{req}\) | Spacing for the target | m |
| \(S_{req}/W\) | Spacing for the target per road width; this is not the S/h uniformity ratio, so compare S with the mounting height separately | - |
Method and standards
Lumen method.
Where it is used
- Plant roads and yards.
- Retrofit checks.
Common mistakes
- Ignoring uniformity.
- Using lamp watts instead of lumens.
Assumptions and limits
- Average values only.
References
- Lumen method for road lighting
- E = ΦCU·MF/(WS) (illuminating engineering practice)
Questions and answers
What is the coefficient of utilisation?
The share of lamp flux that lands on the road strip, from the luminaire's photometric curve.
Why a maintenance factor?
Lamp output falls with age and dirt on the optics; 0.7–0.85 is common for LED road lights.
What do the defaults represent?
15,000 lm LED luminaires every 30 m on one side of an 8 m plant road.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.