Worked example
Example: 2.4 kW, 312 000 lm over 400 m². The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total power of the lighting | 2,400.0 W |
| Total lumens of the lamps | 312,000 - |
| Floor area | 400.00 m² |
| Utilisation factor | 60.000 % |
| Maintenance factor | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Lighting power density | 6.0000 W/m² |
| Efficacy (lumens per watt) | 130.00 |
| Average maintained illuminance (lux) | 374.40 |
| Power per m² per 100 lux (W/m² per 100 lx) | 1.6026 |
Open this example in the calculator and change any input.
Formula
\(LPD = \frac{P}{A}, \quad \eta_L = \frac{\Phi}{P}, \quad E = \frac{\Phi\, UF\, MF}{A}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Total power of the lighting | W |
| \(\Phi\) | Total lumens of the lamps | - |
| \(A\) | Floor area | m² |
| \(UF\) | Utilisation factor | - |
| \(MF\) | Maintenance factor | - |
| \(LPD\) | Lighting power density | W/m² |
| \(\eta_L\) | Efficacy (lumens per watt) | - |
| \(E\) | Average maintained illuminance (lux) | - |
| \(w\) | Power per m² per 100 lux (W/m² per 100 lx) | - |
Method and standards
Lumen method in reverse.
Where it is used
- Lighting energy audits.
- Comparing retrofit options.
Common mistakes
- Lamp lumens for luminaire lumens.
- Ignoring maintenance factor.
Assumptions and limits
- Uniform general lighting.
References
- Lumen method (CIBSE Code for Lighting / IES Lighting Handbook)
Questions and answers
What is the LPD of 2.4 kW over 400 m²?
6 W/m²; with 312 000 lm that is 130 lm/W and 374 lux maintained.
What does W/m² per 100 lux show?
How efficiently the whole installation makes light on the working plane.
What limits apply?
Energy codes set LPD limits by building type; check your local code.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.