Average Daylight Factor of a Room

Average daylight factor of a side-lit room from window area, transmittance, sky angle, room surface area and reflectance, with indoor illuminance.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 6 m² glazing, 150 m² roomControl room 15 m², 300 m²

Results

Average daylight factor formula (Lynes, as used in the BRE and CIBSE guides) with θ in degrees: DF% = TA_wθM/(A(1 − R²)). Above 5 % is well daylit; below 2 % needs electric light much of the day.

Average daylight factor2.3763%
Average indoor daylight illuminance237.63lx

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 6 m² glazing, 150 m² room. The inputs, in the units selected above:

InputValue
Net glazed area6.0000 m²
Glazing light transmittance70.000 %
Visible sky angle from the window centre70.000 °
Maintenance (dirt) factor90.000 %
Total room surface area (floor, ceiling, walls, windows)150.00 m²
Area-weighted average reflectance50.000 %
Outdoor unobstructed sky illuminance10,000 lx

Applying the formula below gives:

ResultValue
Average daylight factor2.3520 %
Average indoor daylight illuminance235.20 lx

Open this example in the calculator and change any input.

Formula

\(DF = \frac{TA_w\theta M}{A(1 - R^2)}\ \text{(}\theta\text{ in degrees, DF in \%)}, \quad E_i = DF\cdot E_o\)

Variables

Symbol Meaning SI unit
\(A_w\) Net glazed area m²
\(T\) Glazing light transmittance -
\(\theta\) Visible sky angle from the window centre rad
\(M\) Maintenance (dirt) factor -
\(A\) Total room surface area (floor, ceiling, walls, windows) m²
\(R\) Area-weighted average reflectance -
\(E_o\) Outdoor unobstructed sky illuminance lx
\(DF\) Average daylight factor -
\(E_i\) Average indoor daylight illuminance lx

Method and standards

Average daylight factor.

Where it is used

  • Control rooms, offices and workshops.
  • Energy savings from daylight.

Common mistakes

  • Using gross window area including frames.
  • Forgetting obstruction in θ.

Assumptions and limits

  • Overcast sky; side-lit room.
  • The formula is empirical in degrees: θ is converted to degrees inside it, and DF comes out in per cent before being shown as a fraction.

References

  • Average daylight factor DF = TA_wθM/(A(1 − R²)) (Lynes; CIBSE Lighting Guide LG10)

Questions and answers

What is daylight factor?

Indoor illuminance as a percentage of the simultaneous outdoor illuminance under an overcast sky.

Why does reflectance matter so much?

Light that enters bounces round the room; the 1/(1 − R²) term captures the inter-reflections.

What do the defaults represent?

6 m² of glazing in a room of 150 m² total surface with mid reflectances and a 70° sky angle.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.