Worked example
Example: 6 m² glazing, 150 m² room. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Net glazed area | 6.0000 m² |
| Glazing light transmittance | 70.000 % |
| Visible sky angle from the window centre | 70.000 ° |
| Maintenance (dirt) factor | 90.000 % |
| Total room surface area (floor, ceiling, walls, windows) | 150.00 m² |
| Area-weighted average reflectance | 50.000 % |
| Outdoor unobstructed sky illuminance | 10,000 lx |
Applying the formula below gives:
| Result | Value |
|---|---|
| Average daylight factor | 2.3520 % |
| Average indoor daylight illuminance | 235.20 lx |
Open this example in the calculator and change any input.
Formula
\(DF = \frac{TA_w\theta M}{A(1 - R^2)}\ \text{(}\theta\text{ in degrees, DF in \%)}, \quad E_i = DF\cdot E_o\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_w\) | Net glazed area | m² |
| \(T\) | Glazing light transmittance | - |
| \(\theta\) | Visible sky angle from the window centre | rad |
| \(M\) | Maintenance (dirt) factor | - |
| \(A\) | Total room surface area (floor, ceiling, walls, windows) | m² |
| \(R\) | Area-weighted average reflectance | - |
| \(E_o\) | Outdoor unobstructed sky illuminance | lx |
| \(DF\) | Average daylight factor | - |
| \(E_i\) | Average indoor daylight illuminance | lx |
Method and standards
Average daylight factor.
Where it is used
- Control rooms, offices and workshops.
- Energy savings from daylight.
Common mistakes
- Using gross window area including frames.
- Forgetting obstruction in θ.
Assumptions and limits
- Overcast sky; side-lit room.
- The formula is empirical in degrees: θ is converted to degrees inside it, and DF comes out in per cent before being shown as a fraction.
References
- Average daylight factor DF = TA_wθM/(A(1 − R²)) (Lynes; CIBSE Lighting Guide LG10)
Questions and answers
What is daylight factor?
Indoor illuminance as a percentage of the simultaneous outdoor illuminance under an overcast sky.
Why does reflectance matter so much?
Light that enters bounces round the room; the 1/(1 − R²) term captures the inter-reflections.
What do the defaults represent?
6 m² of glazing in a room of 150 m² total surface with mid reflectances and a 70° sky angle.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.