Battery Run Time with Peukert's Law

Run time of a battery at a discharge current by Peukert's law from its rated capacity, rated discharge time and Peukert exponent, with the capacity delivered.

Thermal power plant

Inputs

Examples: 100 Ah (20 h) at 10 A, k 1.2200 Ah (10 h) at 50 A, k 1.25, 80 % DoD100 Ah (20 h) at 5 A, k 1.0 (at the rated rate)

From the battery maker, or from two discharge tests; 1 means no loss of capacity with rate.

Results

Peukert's law was fitted to lead–acid batteries at constant current and temperature; lithium cells lose much less capacity with rate.

Run time to the allowed depth of discharge2.5449h
Run time ignoring the Peukert effect3.2000h
Capacity delivered at this current (to full discharge)159.05Ah

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100 Ah (20 h) at 10 A, k 1.2. The inputs, in the units selected above:

InputValue
Rated capacity100.00 Ah
Rated discharge time (the rate the capacity is quoted at)20.000 h
Discharge current10.000 A
Peukert exponent1.2000 -
Depth of discharge allowed100.00 %

Applying the formula below gives:

ResultValue
Run time to the allowed depth of discharge8.7055 h
Run time ignoring the Peukert effect10.000 h
Capacity delivered at this current (to full discharge)87.055 Ah

Open this example in the calculator and change any input.

Formula

\(t = DoD \cdot H \left(\frac{C}{I\, H}\right)^k\)

\(t_0 = DoD \cdot \frac{C}{I}, \qquad C_{eff} = I\, H \left(\frac{C}{I\, H}\right)^k\)

Variables

Symbol Meaning SI unit
\(C\) Rated capacity C
\(H\) Rated discharge time (the rate the capacity is quoted at) s
\(I\) Discharge current A
\(k\) Peukert exponent -
\(DoD\) Depth of discharge allowed -
\(t\) Run time to the allowed depth of discharge s
\(t_0\) Run time ignoring the Peukert effect s
\(C_{eff}\) Capacity delivered at this current (to full discharge) C

Method and standards

Peukert's empirical law referred to the rated discharge time.

Where it is used

  • UPS and inverter backup estimates.
  • Solar battery planning.

Common mistakes

  • Using the 20 h capacity at a 1 h rate.
  • Applying it to lithium cells.

Assumptions and limits

  • Constant current and temperature.
  • Below the rated rate (I < C/H) the law extrapolates above the rated capacity; real batteries rarely deliver it.

References

  • W. Peukert
  • Elektrotechnische Zeitschrift 20 (1897); form t = H (C / (I H))^k

Questions and answers

How long does a 100 Ah (20 h) battery last at 10 A with k = 1.2?

8.7 h, delivering 87 Ah instead of 100.

What exponent should I use?

The maker's; flooded lead–acid is higher than AGM or gel.

Why less than rated?

At high current the plates cannot give up all their charge before the voltage collapses.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.