FireCADCalc

Battery Internal Resistance and Terminal Voltage

Internal resistance of a battery from open-circuit and on-load voltages, and the terminal voltage, loss and short-circuit current at another load.

Thermal power plantElectrician and wireman licence examinations

Inputs

Examples: 12 V batteryStation cell 2.1 V

Results

Internal resistance rises with age, cold and low charge; compare readings over time.

Internal resistance0.001000Ω
Terminal voltage at I₂1.8500V
Internal loss at I₂0.090000kW
Prospective short-circuit current E/r2,150.0A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 12 V battery. The inputs, in the units selected above:

InputValue
Open-circuit voltage12.700 V
Terminal voltage on load12.100 V
Load current for that reading50.000 A
Another load current150.00 A

Applying the formula below gives:

ResultValue
Internal resistance0.012000 Ω
Terminal voltage at I₂10.900 V
Internal loss at I₂0.27000 kW
Prospective short-circuit current E/r1,058.3 A

Open this example in the calculator and change any input.

Formula

\(r = \frac{E - V_1}{I_1}, \quad V_2 = E - I_2 r, \quad P_r = I_2^2 r, \quad I_{sc} = \frac{E}{r}\)

Variables

Symbol Meaning SI unit
\(E\) Open-circuit voltage V
\(V_1\) Terminal voltage on load V
\(I_1\) Load current for that reading A
\(I_2\) Another load current A
\(r\) Internal resistance Ω
\(V_2\) Terminal voltage at I₂ V
\(P_r\) Internal loss at I₂ W
\(I_{sc}\) Prospective short-circuit current E/r A

Method and standards

Thevenin model.

Where it is used

  • Station and UPS batteries.
  • Electrician examinations.

Common mistakes

  • Reading before the voltage settles.
  • Ignoring lead resistance.

Assumptions and limits

  • Linear model.

References

  • V = E − I r (Thevenin model)

Questions and answers

12.7 V open, 12.1 V at 50 A?

r = 12 mΩ; at 150 A about 10.9 V; short-circuit about 1,058 A.

Why measure it?

It shows ageing before capacity tests do.

Station batteries?

Track each cell's resistance against its baseline.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.