Worked example
Example: 12 V battery. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Open-circuit voltage | 12.700 V |
| Terminal voltage on load | 12.100 V |
| Load current for that reading | 50.000 A |
| Another load current | 150.00 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Internal resistance | 0.012000 Ω |
| Terminal voltage at I₂ | 10.900 V |
| Internal loss at I₂ | 0.27000 kW |
| Prospective short-circuit current E/r | 1,058.3 A |
Open this example in the calculator and change any input.
Formula
\(r = \frac{E - V_1}{I_1}, \quad V_2 = E - I_2 r, \quad P_r = I_2^2 r, \quad I_{sc} = \frac{E}{r}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | Open-circuit voltage | V |
| \(V_1\) | Terminal voltage on load | V |
| \(I_1\) | Load current for that reading | A |
| \(I_2\) | Another load current | A |
| \(r\) | Internal resistance | Ω |
| \(V_2\) | Terminal voltage at I₂ | V |
| \(P_r\) | Internal loss at I₂ | W |
| \(I_{sc}\) | Prospective short-circuit current E/r | A |
Method and standards
Thevenin model.
Where it is used
- Station and UPS batteries.
- Electrician examinations.
Common mistakes
- Reading before the voltage settles.
- Ignoring lead resistance.
Assumptions and limits
- Linear model.
References
- V = E − I r (Thevenin model)
Questions and answers
12.7 V open, 12.1 V at 50 A?
r = 12 mΩ; at 150 A about 10.9 V; short-circuit about 1,058 A.
Why measure it?
It shows ageing before capacity tests do.
Station batteries?
Track each cell's resistance against its baseline.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.