Battery Charging Time and Charge Energy

Time to recharge a battery bank from its capacity, depth of discharge, charging current and charge efficiency, with the C-rate and the energy drawn from the charger.

Thermal power plant

Inputs

Examples: 200 Ah, 80 % back, 20 A, 85 %, 27.6 V110 V station battery 300 Ah, 50 %, 30 A, 85 %, 123 VLithium 100 Ah, 90 %, 50 A, 98 %, 54 V

Lead-acid batteries are lower than lithium-ion; from the battery maker.

Results

Constant-current estimate: the last 10–20 % of charge is slower once the charger switches to constant voltage.

Charging time5.8824h
Charge to put in176.47Ah
Charging rate (C-rate, per hour)0.10000
Energy delivered by the charger (DC side)21.706kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 200 Ah, 80 % back, 20 A, 85 %, 27.6 V. The inputs, in the units selected above:

InputValue
Battery capacity200.00 Ah
Depth of discharge to put back80.000 %
Charging current20.000 A
Charge (ampere-hour) efficiency85.000 %
Average charging voltage27.600 V

Applying the formula below gives:

ResultValue
Charging time9.4118 h
Charge to put in188.24 Ah
Charging rate (C-rate, per hour)0.10000
Energy delivered by the charger (DC side)5.1953 kWh

Open this example in the calculator and change any input.

Formula

\(Q_{in} = \frac{C \cdot DoD}{\eta_c}\)

\(t = Q_{in} / I\)

\(I / C, \quad E_{in} = Q_{in} U_c\)

Variables

Symbol Meaning SI unit
\(C\) battery capacity C (A·s)
\(DoD\) depth of discharge to put back -
\(I\) charging current A
\(\eta_c\) charge (Ah) efficiency -
\(U_c\) average charging voltage V
\(t\) charging time s
\(Q_{in}\) charge to put in C
\(I / C\) charging rate, per hour 1/h
\(E_{in}\) Energy delivered by the charger (DC side) J

Method and standards

The charge removed is capacity times depth of discharge; more must go back because of charge inefficiency. At constant current the time is charge over current; energy is charge times average charging voltage.

Where it is used

  • Sizing a battery charger for a recharge time.
  • Planning UPS and DC system recovery after an outage.
  • Estimating charging energy.

Common mistakes

  • Forgetting charge efficiency.
  • Charging faster than the battery maker allows.
  • Ignoring the constant-voltage taper at the end.

Assumptions and limits

  • Constant-current estimate.
  • Charge efficiency from the battery maker.
  • E_in is the DC energy into the battery; the energy from the mains is E_in divided by the charger (rectifier) efficiency.
  • The C/3 warning is an indicative screening level, not a standard limit; the battery maker's maximum charging current governs.

References

  • Ampere-hour balance

Questions and answers

How long to recharge a 200 Ah battery from 80 % discharge at 20 A?

About 9.4 hours with 85 % charge efficiency: 160 Ah must go back, 188 Ah in from the charger.

What is the C-rate?

Charging current divided by capacity, per hour: 20 A into 200 Ah is C/10, a typical rate for lead-acid.

Why does charging take longer than this?

Chargers switch to constant voltage near full charge and the current tapers, so the last 10–20 % takes longer.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.