Worked example
Example: Switchgear: 60 A 1 min, 20 A 2 h, 100 A 1 min. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Load current, period 1 | 60.000 A |
| Duration of period 1 | 1.0000 min |
| Load current, period 2 | 20.000 A |
| Duration of period 2 | 120.00 min |
| Load current, period 3 | 100.00 A |
| Duration of period 3 | 1.0000 min |
| Temperature correction factor (rated capacity at 25 °C; 1 at or above 25 °C) | 1.1100 - |
| Ageing factor | 1.2500 - |
| Design margin | 1.1000 - |
| Usable depth of discharge | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Load ampere-hours | 42.667 Ah |
| Rated capacity, ampere-hour estimate (check by IEEE 485 for short high currents) | 81.400 Ah |
| Highest load current | 100.00 A |
Open this example in the calculator and change any input.
Formula
\(Ah = \sum I_it_i, \quad C = \frac{Ah\cdot k_Tk_Ak_D}{DoD}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_1\) | Load current, period 1 | A |
| \(t_1\) | Duration of period 1 | s |
| \(I_2\) | Load current, period 2 | A |
| \(t_2\) | Duration of period 2 | s |
| \(I_3\) | Load current, period 3 | A |
| \(t_3\) | Duration of period 3 | s |
| \(k_T\) | Temperature correction factor (rated capacity at 25 °C) | - |
| \(k_A\) | Ageing factor | - |
| \(k_D\) | Design margin | - |
| \(DoD\) | Usable depth of discharge | - |
| \(Ah_{load}\) | Load ampere-hours (charge) | C (shown in Ah) |
| \(C\) | Rated capacity, ampere-hour estimate | C (shown in Ah) |
| \(I_{max}\) | Highest load current | A |
Method and standards
Ampere-hour method.
Where it is used
- Substation and power plant DC systems.
- Emergency lighting batteries.
Common mistakes
- Forgetting the end-of-life margin.
- Sizing on ampere-hours only for high short currents.
Assumptions and limits
- Ampere-hour basis: the result is a first estimate. Short high-current periods (breaker trip and close, motor starts) need more capacity than their ampere-hours suggest; confirm the size by the IEEE 485 section method with the maker's discharge curves.
- Rated capacity referred to 25 °C; the temperature factor is 1 or more (a warmer room is not credited).
References
- Ampere-hour sizing with temperature
- ageing and design margins (IEEE 485 factors; definitions)
Questions and answers
Why an ageing factor of 1.25?
Batteries are replaced at 80 % of rated capacity; sizing 25 % up keeps the duty met to end of life.
Why a temperature factor?
Lead-acid capacity falls in the cold: about 11 % more is needed at 15 °C than at 25 °C.
What do the defaults represent?
A switchgear battery: 60 A tripping for one minute, 20 A standing load for two hours, then 100 A closing for one minute.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.