Results

Distance from the lamp to the point3.0000m
Angle of incidence0°
Illuminance on the horizontal surface (lux)133.33
Illuminance on a surface facing the lamp (lux)133.33

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 000 cd, 6 m high, 4 m to the side. The inputs, in the units selected above:

InputValue
Luminous intensity in the direction of the point, I(θ) (candela)5,000.0 -
Mounting height above the surface6.0000 m
Horizontal distance from the point below the lamp4.0000 m

Applying the formula below gives:

ResultValue
Distance from the lamp to the point7.2111 m
Angle of incidence33.690 °
Illuminance on the horizontal surface (lux)80.005
Illuminance on a surface facing the lamp (lux)96.154

Open this example in the calculator and change any input.

Formula

\(E_h = \frac{I \cos\theta}{d^2} = \frac{I\, h}{(h^2 + x^2)^{3/2}}, \quad E_n = \frac{I}{d^2}\)

Variables

Symbol Meaning SI unit
\(I\) Luminous intensity in the direction of the point, I(θ) (candela) -
\(h\) Mounting height above the surface m
\(x\) Horizontal distance from the point below the lamp m
\(d\) Distance from the lamp to the point m
\(\theta\) Angle of incidence rad
\(E_h\) Illuminance on the horizontal surface (lux) -
\(E_n\) Illuminance on a surface facing the lamp (lux) -

Method and standards

Point-source photometry.

Where it is used

  • Flood, street and task lighting checks.
  • Electrical examinations.

Common mistakes

  • Using lumens for candela.
  • Forgetting the cosine.

Assumptions and limits

  • Point source, no reflections.
  • I is the intensity in the direction of the point, I(θ), from the luminaire's polar curve; the nadir (0°) value applies only to the point directly below.

References

  • Inverse-square law and Lambert's cosine law

Questions and answers

What lux does 5000 cd give 4 m to the side from 6 m high?

80.0 lux on the floor; 139 lux directly below.

Why does it fall so fast to the side?

Distance grows and the light strikes at a slant: the cos³ law.

When is the lumen method better?

For average illuminance of a room with many fittings and reflections.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.