Battery Bank Voltage, Capacity and Energy (Series–Parallel)

Voltage, ampere-hour capacity and stored energy of a battery bank from the cell or block rating and the number connected in series and in parallel.

Thermal power plantElectrician and wireman licence examinations

Inputs

Examples: Eight 12 V 150 Ah: 4 in series, 2 strings110 cells of 2 V 400 Ah in series3.2 V 100 Ah LFP cells: 16 in series, 3 strings

Results

Bank voltage220.00V
Bank capacity400.00Ah
Stored energy (nominal)88.000kWh
Batteries in the bank110.00

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Eight 12 V 150 Ah: 4 in series, 2 strings. The inputs, in the units selected above:

InputValue
Voltage of one battery or cell12.000 V
Capacity of one battery150.00 Ah
Batteries in series per string4.0000 -
Strings in parallel2.0000 -

Applying the formula below gives:

ResultValue
Bank voltage48.000 V
Bank capacity300.00 Ah
Stored energy (nominal)14.400 kWh
Batteries in the bank8.0000

Open this example in the calculator and change any input.

Formula

\(V = n_s V_b, \quad C = n_p C_b, \quad E = V\, C\)

Variables

Symbol Meaning SI unit
\(V_b\) Voltage of one battery or cell V
\(C_b\) Capacity of one battery C
\(n_s\) Batteries in series per string -
\(n_p\) Strings in parallel -
\(V\) Bank voltage V
\(C\) Bank capacity C
\(E\) Stored energy (nominal) J
\(n\) Batteries in the bank -

Method and standards

Series and parallel combination of identical batteries.

Where it is used

  • Solar, UPS and telecom banks.
  • Inverter battery planning.

Common mistakes

  • Mixing old and new batteries.
  • Counting Ah of series batteries twice.

Assumptions and limits

  • Identical batteries.
  • Numbers in series and in parallel are rounded to whole numbers, with a note.

References

  • Kirchhoff's circuit laws (series voltages add, parallel currents add)

Questions and answers

What do eight 12 V 150 Ah batteries give as 4 in series, 2 strings?

48 V, 300 Ah, 14.4 kWh nominal.

Is all of that usable?

No: depth-of-discharge limits and the discharge rate reduce it.

Why avoid many parallel strings?

They share current unevenly; fewer, larger cells are better.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.