Boiler Blowdown Rate (TDS Balance)

Continuous blowdown needed to hold boiler water dissolved solids at a limit, with feedwater flow, cycles of concentration and the heat lost in the blowdown.

Inputs

Examples: Shell boiler 10 t/h, feed 150 ppm, limit 3 000 ppmWater-tube 50 t/h, feed 50 ppm, limit 1 500 ppmHP drum 120 t/h, feed 5 ppm, limit 150 ppm

TDS (or the controlling species, e.g. silica) by mass in the feedwater entering the drum.
The limit for the boiler pressure from the boiler maker or the water-chemistry guideline.
Absolute. Choose a gauge unit to enter gauge readings.

Results

Blowdown flow4,137.9kg/h
Blowdown as a share of steam3.4483%
Blowdown as a share of feedwater3.3333%
Feedwater flow124,138kg/h
Cycles of concentration30.000
Heat leaving with the blowdown (above feedwater)526.79kW
Boiler water enthalpy (saturated liquid)1,450.3kJ/kg
Feedwater enthalpy991.97kJ/kg

Download PDF Link to this result

Log in to save calculations to your dashboard.

Formula

Dissolved solids enter only with the feedwater and leave only with the blowdown (steam carries none):

\(F\,c_{fw} = B\,c_{bd} \qquad F = S + B \quad\Rightarrow\quad B = \frac{S\,c_{fw}}{c_{bd} - c_{fw}}\)

\(N = \frac{c_{bd}}{c_{fw}} \qquad B/F = \frac{c_{fw}}{c_{bd}} \qquad \dot Q_{bd} = B\,(h_f - h_{fw})\)

Variables

Symbol Meaning SI unit
\(S\) steam generated kg/s
\(c_{fw}\) dissolved solids in feedwater (mass fraction) –
\(c_{bd}\) maximum dissolved solids in boiler water –
\(p\) drum absolute pressure Pa
\(T_{fw}\) feedwater temperature K
\(B\) blowdown flow kg/s
\(B/S\) blowdown as a share of steam –
\(B/F\) blowdown as a share of feedwater –
\(F\) feedwater flow kg/s
\(N\) cycles of concentration –
\(\dot Q_{bd}\) heat leaving with the blowdown, above feedwater W
\(h_{f}\) saturated liquid enthalpy at drum pressure J/kg
\(h_{fw}\) feedwater enthalpy J/kg

Method and standards

Steady-state mass balance on dissolved solids, the standard basis for continuous blowdown control. Enthalpies from FireCAD's IAPWS-IF97 implementation. Boiler-water limits are the user's input, taken from the boiler maker or a recognised water-chemistry guideline for the drum pressure.

Assumptions and limits

  • Steady state; no solids carried over with the steam and none removed by intermittent (bottom) blowdown.
  • Concentrations by mass (ppm = mg/kg); for dilute water mg/L is the same number.
  • Feedwater enthalpy at drum pressure.

References

  • IAPWS R7-97(2012) IF97
  • ASME water chemistry guidelines (limits)

Questions and answers

How is blowdown calculated?

By a dissolved-solids balance. Solids enter with the feedwater and leave only with the blowdown, so B = S·c_fw/(c_bd − c_fw). For 10 t/h with 150 ppm feed and a 3 000 ppm limit, B = 526 kg/h, 5.3 % of the steam.

Where do the boiler-water limits come from?

From the boiler maker or a water-chemistry guideline for the drum pressure and the controlling species (TDS, silica, alkalinity, chloride). Use the species that gives the highest blowdown.

Why does the heat loss matter?

Blowdown leaves as saturated water at drum pressure. For a 50 t/h boiler at 45 bar(a) blowing down 3.4 % of steam, about 254 kW leaves above the feedwater enthalpy; a flash vessel and cooler can recover most of it.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.