Three-Phase Motor Full-Load Current and Power

Full-load current, input power, apparent and reactive power of a three-phase motor from rating, voltage, efficiency and power factor.

Inputs

Examples: 11 kW, 400 V55 kW, 415 V1 000 kW feed pump, 6.6 kV75 hp, 460 V

Results

Electrical input power1,041.7kW
Full-load line current101.25A
Apparent power1,157.4kVA
Reactive power504.50kvar
Motor losses (heat)41.667kW

Download PDF Link to this result

Log in to save calculations to your dashboard.

Formula

\(P_{in} = \frac{P_{out}}{\eta} \qquad S = \frac{P_{in}}{\cos\varphi} \qquad I = \frac{S}{\sqrt{3}\,U} = \frac{P_{out}}{\sqrt{3}\,U\,\eta\,\cos\varphi} \qquad Q = \sqrt{S^2 - P_{in}^2} \qquad P_{loss} = P_{in} - P_{out}\)

Variables

Symbol Meaning SI unit
\(U\) line-to-line voltage V
\(P_{out}\) rated mechanical output at the shaft W
\(\eta\) efficiency at full load –
\(\cos\varphi\) power factor at full load –
\(P_{in}\) active electrical input W
\(I\) line current A
\(S\) apparent power VA
\(Q\) reactive power var
\(P_{loss}\) losses dissipated as heat W

Method and standards

Balanced three-phase power relations, with efficiency and power factor as defined in IEC 60034-1. The output may be entered in kW or horsepower (1 hp = 745.70 W mechanical; 1 metric hp = 735.50 W).

Assumptions and limits

  • Balanced three-phase supply at rated voltage and frequency.
  • Full-load values of efficiency and power factor; both change with load.

References

  • IEC 60034-1 (rating and performance definitions)
  • IEC 60034-30-1 (efficiency classes)

Questions and answers

Why is the current higher than P/(√3·U)?

The shaft output is only part of what the motor draws. Losses raise the active power to P/η, and the power factor means the current carries reactive power as well, so I = P/(√3·U·η·cosφ).

Which efficiency and power factor should I use?

The nameplate or data-sheet values at full load. Both fall at part load; for a motor running at 50 % load use the part-load values from the manufacturer's curve.

Is this the starting current?

No. Direct-on-line starting current is typically 6 to 8 times the full-load current for a few seconds.